Siemens SENTRON 3VL160X System Manual page 81

Iec molded case circuit breakers
Hide thumbs Also See for SENTRON 3VL160X:
Table of Contents

Advertisement

Table 6- 2
Permissible safety clearances in accordance with IEC 60947
Molded
Switching
case circuit
capacity
breaker
type
VL160X
N, H
VL160
N, H, L
VL250
N, H, L
VL400
N, H, L
VL630
N, H, L
VL800
N, H, L
VL1250
N, H, L
VL1600
N, H, L
N: Standard
H: High
L: Very high
Figure 6-1
Figure 6-2
Table 6- 3
A:
B:
C:
D:
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
Minimum
A ≤ 415 V
footprint
With or
without
covers
m
3
0,011
35 mm
0,011
50 mm
0,015
50 mm
0,036
50 mm
0,18
50 mm
0,22
50 mm
0,22
70 mm
0,264
100 mm
Safety clearances
No minimum clearance between two horizontally or vertically installed molded case
circuit breakers
Definition of the permissible safety clearances in [mm] between
Molded case circuit breakers and busbars (uninsulated and grounded metal); terminal cover
required above 600 V AC, 500 V DC
Molded case circuit breaker terminal and lower panel
Sides of the molded case circuit breaker and side panels left / right (uninsulated and grounded
metal)
Molded case circuit breaker and non-conductive parts with at least 3 mm thick insulation
(insulator, insulated bar, painted plate)
A > 415-690 V
Without
With
covers
covers
70 mm
35 mm
100 mm
50 mm
100 mm
50 mm
100 mm
50 mm
100 mm
50 mm
100 mm
50 mm
100 mm
70 mm
100 mm
100 mm
Installing/mounting
6.2 Mounting and safety clearances
B ≤ 690 V
C ≤ 690 V
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm
30 mm
30 mm
100 mm
30 mm
D ≤ 690 V
35 mm
35 mm
35 mm
35 mm
35 mm
35 mm
50 mm
100 mm
81