Circuit diagrams
Circuit diagrams, undervoltage release and shunt release
Undervoltage release and shunt release for VL160X to VL1600
S01
S02
S03
K1
Figure 13-7
Protective circuit with UVR
(220 V to 250 V DC)
Y2 only
Y2 and Y1 bridged
Protective circuit with UVR and contactor
Y2 only
Y2 and Y1 bridged
300
"S contat" integrated into
shunt release
Delayed release
Instantaneous release for EMERGENCY-OFF loop (if required)
Leading auxiliary contact, e.g. 3VL9300-3AS10 "OFF to ON" in the front-operated rotary
operating mechanism of the molded case circuit breaker (if required)
Auxiliary contactor 3RH11 (if required)
Time-delay device (3TX4701-0A) for undervoltage release for VL160X to VL1600
Tripping time UVR
Approx. 3 seconds
Approx. 6 seconds
Tripping time UVR
0.8 s
1.2 s
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
Drop-out time contactor
Approx. 2 s
Approx. 4 s