Siemens SENTRON 3VL160X System Manual page 162

Iec molded case circuit breakers
Hide thumbs Also See for SENTRON 3VL160X:
Table of Contents

Advertisement

Technical data
11.12 Shunt release
Table 11- 41 Shunt release for VL630 to VL1600
Response voltage: Pick-up (circuit breaker
trips) [V]
Power consumption
AC 50 / 60 Hz [VA]
DC [W]
Max. in-service period [s]
Max. opening time [ms]
Fuse (slow) [A]
Molded case circuit breaker, [A]
C characteristic
Note
The power consumption of the shunt releases for approx. 20 ms should be taken into
account when selecting the power supply for the control circuit, for example by means of a
corresponding short-time overload capability of the power supply used.
162
VL630
0.7-1.10 U
24
480
48-60 V
401 - 501
110-127 V
424 - 489
208-277 V
533 - 736
380-600 V
408 - 645
24 V
594
48-60 V
740 - 925
110-127 V
559 - 648
220-250 V
722 - 820
20
(AC 24, 48-60, 110-127 V, 208-277 V)
VL800
VL1200
0.7-1.10 U
0.7-1.10 U
s
s
480
480
401 - 501
401 - 501
424 - 489
424 - 489
533 - 736
533 - 736
408 - 645
408 - 645
594
594
740 - 925
740 - 925
559 - 648
559 - 648
722 - 820
722 - 820
Interrupts automatically
20
20
4
2
(all others)
5
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
VL1600
0.7-1.10 U
s
s
480
401 - 501
424 - 489
533 - 736
408 - 645
594
740 - 925
559 - 648
722 - 820
20