Step 3—Fan Adjustment Check
This furnace is equipped with a variable speed motor to deliver a
constant airflow. Adjust DIP switches on the electronic board
ACCORDING TO OIL INPUT SELECTED AND A/C SIZE. (See
Tables 11A, 11B, and 11C or Tables 12A, 12B and 12C.)
Table 11a—58VMR105 Dip Switch Adjustment for
Oil Heating Mode
SW1-HEAT
DIP SWITCH
INPUT
POSITION
USGPH
1
2
OFF
OFF
0.75
ON
OFF
0.65
OFF
ON
0.5
ON
ON
N/A
Table 11b—58VMR105 Size Dip Switch
Adjustments for Heat Pump and Cooling Mode
SW2-COOL
DIP SWITCH POSITION
1
OFF
ON
OFF
ON
Table 11c—58VMR105 Size Dip Switch CFM
Adjustments in All Modes
SW2-ADJUST
HEATING CFM %
DIP SWITCH POSITION
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
FIRE HAZARD AND UNIT RELIABILITY
Failure to follow this warning could result in property
damage, personal injury or death.
When operating furnace in heating mode, static pressure and
temperature rise (supply-air temperature minus return-air
temperature) must be within those limits specified on rating
label.
Step 4—Limit Control Check
After furnace has been in operation for at least 15 minutes, restrict
return-air supply by blocking filters or closing return registers and
allow furnace to shut down on high limit. The burner should shut
off, and main blower should continue to run.
Step 5—For Year-Round Air Conditioning
This furnace is designed for use in conjunction with cooling
equipment to provide year-round air conditioning. The blower has
been sized for both heating and cooling, however, fan motor
setting may need to be changed to obtain necessary cooling
airflow.
Step 6—Heating
The blower speed is factory set to deliver required airflow at
normal duct static pressure for 0.75 GAL/HR (US) INPUT for the
SW4-DELAY
DIP SWITCH
INPUT
POSITION
USGPH
1
2
OFF
OFF
0.75
ON
OFF
0.65
OFF
ON
0.5
ON
ON
N/A
A/C SIZE
(TONS)
2
OFF
3.0
OFF
2.5
ON
2.0
ON
1.5
COOLING CFM %
INCREASE OR
INCREASE OR
DECREASE
DECREASE
0
0
+ 13
+ 10
- 15
- 10
N/A
0
58VMR105 size (See Table 11A, 11B, and 11C) and 0.85
GAL/HR (US) INPUT for the 58VMR120 size. (See Table 12A,
12B, and 12C.) The blower motor may be field adjusted to deliver
required airflow for other capacity.
Table 12a—58VMR120 Dip Switch Adjustment for
Oil Heating Mode
SW1-HEAT
DIP SWITCH
POSITION
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Table 12b—58VMR120 Size Dip Switch
Adjustments for Heat Pump and Cooling Mode
SW2-COOL
DIP SWITCH POSITION
1
OFF
ON
OFF
ON
Table 12c—Dip Switch CFM Adjustments in All
SW2-ADJUST
DIP SWITCH POSITION
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Step 7—Cooling
The blower may be field adjusted to deliver required airflow for
cooling application. (See Table 13 and 14.)
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in possible damage
to this equipment, serious personal injury, or death.
The ability to properly perform maintenance on this equip-
ment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User's Manual.
ELECTRICAL SHOCK HAZARD
Failure to comply with this warning could cause electrical
shock resulting in personal injury or death.
Before performing any service functions, unless operations
specifically require power to be on, make sure all utilities are
turned off upstream of appliance.
12
SW4-DELAY
DIP SWITCH
INPUT
POSITION
USGPH
1
2
0.85
OFF
OFF
1.00
ON
OFF
1.10
OFF
ON
N/A
ON
ON
A/C SIZE
(TONS)
2
OFF
OFF
ON
ON
Modes
HEATING CFM %
COOLING CFM %
INCREASE OR
INCREASE OR
DECREASE
DECREASE
0
+ 13
- 15
N/A

MAINTENANCE

INPUT
USGPH
0.85
1.00
1.10
N/A
5.0
4.0
3.5
3.0
0
+ 10
- 10
0