Start-Up, Adjustment, And Safety Checkout; Operational Checkout; Combustion Check - Carrier 110 Series Installation, Start-Up, And Operating Instructions Manual

Multipoise oil furnace, for input capacities of 70,000-154,000
Table of Contents

Advertisement

START-UP, ADJUSTMENT, AND SAFETY CHECKOUT

Step 1—Operational Checkout
Installation of furnace is now complete. Run through the following
checkout and ensure each item has been performed.
1. Correct nozzle size has been selected for desired input rate.
2. Blower wheel support is removed.
3. Electrical wiring is completed according to Fig. 3.
4. Blower access door is secured in place.
5. Valve on oil supply line is open.
6. RESET BUTTON on primary control is pushed down.
7. Flame observation door and 2 cleanout access doors located at
front of unit are closed.
8. Thermostat is set for heating mode and set above room
temperature.
If all of the above items have been performed, set main electrical
switch to ON position and burner should start. When burner starts,
proceed to Combustion Check section.
Step 2—Combustion Check
In order to obtain optimum performance from oil burner, the
following setup procedures must be followed:
1. A test kit to measure smoke, stack draft, over-fire draft, CO
oil pump pressure, and stack temperatures MUST be used in
order to obtain proper air band setting. Although all of the
above measurements are required for optimum setup and
efficiency data, the most important readings that must be taken
are smoke number, over-fire draft, stack draft, and oil pump
pressure.
2. The proper smoke number has been established by engineer-
ing tests to be between 0 and 1. This degree of smoke emission
is commonly referred to as a "trace" of smoke. It is recom-
mended to use a Bacharach true spot smoke test set or
equivalent.
Table 9—Furnace Draft Conditions
(In. wc)
FURNACE
FLUE
OVER-FIRE
INPUT
DRAFT
DRAFT
(BTUH)
MINIMUM
MAXIMUM
70,000
-0.025
91,000
-0.025
105,000
-0.025
119,000
-0.025
140,000
-0.025
154,000
-0.025
3. In order to ensure proper draft through furnace, a barometric
draft regulator (supplied with furnace) must be installed.
In order for this device to function properly, barometric damper
must be mounted with hinge pins horizontal and face of damper
vertical. (See instructions included with damper.) The draft regu-
lator should be adjusted after furnace has been firing for at least 5
minutes, and set between -0.025 and -0.035 in. wc. (See Table 9.)
4. The over-fire draft, which is taken through observation door
(located in center line above burner in front panel of furnace),
is a measurement necessary to determine if there is a blockage
between oil burner and flue outlet.
There should be a total pressure drop of between 0.020 and 0.05 in.
wc through furnace as shown in Table 9. The over-fire draft must
be set within the range shown in Table 9.
TOTAL RESTRICTION
THROUGH
HEAT EXCHANGER
0.010
0.020 to 0.035
0.020
0.030 to 0.045
0.025
0.035 to 0.050
0.025
0.035 to 0.050
0.025
0.035 to 0.050
0.025
0.035 to 0.050
A reading outside the range shown in Table 9 (for example +0.1 in.
wc) would indicate that furnace is in an extremely high-pressure
condition in primary section. This condition may be caused by any
of the following problems:
a. Excessive combustion air due to air band being too wide
open.
b. A lack of flue draft (chimney effect) or some other
blockage, such as soot, in secondary section of heat
exchanger.
c. Use of an oversized nozzle input.
d. Pump pressure over the values listed in Table 10.
Table 10—Burner Input And Nozzle Size
FURNACE
FIRING
INPUT
RATE
(BTUH)
GAL/HR (US)*
70,000
0.50
91,000
0.65
105,000
0.75
119,000
0.85
140,000
1.00
154,000
1.10
* For Rating Purposes Only
,
2
5. The CO
and stack temperature instruments enable you to
2
obtain data required to determine thermal efficiency of fur-
nace.
6. An oil filter should be installed as close to burner as possible
with ALL oil burners and is essential on lower firing rate
burners. We recommend the use of a low pressure drop oil
filter such as the General Filter, Inc. model #1A-25A or
equivalent.
7. The oil pressure regulator is factory set to give oil pressure of
135 psig for the model having 105,000 BTUH input and 130
psig for the model having 119,000 BTUH input. The firing
rate noted on nameplate may be obtained using the nozzles
and pump pressures indicated in Table 10. The proper oil
burner turbulator setting for all the firing rates is 0 (zero).
8. On a new installation, air entrapped in oil line leading from
tank to nozzle must be thoroughly purged in order to prevent
excessive after drip. The oil pump is provided with a special
fitting which allows purging of any air between tank and oil
pump. The proper procedure for performing this operation is
as follows:
a. Place a piece of clear plastic 1/4-in. diameter tubing over
purge fitting on oil pump.
b. Start oil burner, then open purge fitting and allow burner to
run until purge tube is completely free of air bubbles.
c. Tighten purge fitting. Allow oil to run to nozzle and fire
burner.
d. If purging takes longer than 15 sec and no flame has been
established, burner stops. Push reset button on front of
primary control to restart burner.
e. For detailed information on operation of primary control,
refer to instructions included with furnace.
After all the setup procedures mentioned above have been com-
pleted, the burner should be allowed to operate and an inspection
mirror should be used to observe the flame pattern at tip of nozzle.
Any irregularities such as burning to 1 side or pulsating flame
patterns should be corrected by changing nozzle.
10
RIELLO OIL BURNER
PUMP
PRESSURE
No. 40 Series
Delavan
(PSIG)
Model
Nozzle
F3
0.40 - 70A
160
F3
0.50 - 70W
170
F3
0.65 - 70W
135
F5
0.75 - 70B
130
F5
0.85 - 70W
140
F5
1.00 - 70W
125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58vmr

Table of Contents