Connection establishment and termination
Connections are established using the program block TCON. Note that a separate program
block TCON must be called for each connection.
A separate connection must be established for each communications partner even if
identical blocks of data are being sent.
After a successful transfer of the data, a connection can be terminated. A connection is also
terminated by calling TDISCON.
Note
Connection abort
If an existing connection is aborted by the communications partner or due to disturbances on
the network, the connection must also be terminated by calling TDISCON. Make sure that
you take this into account in your programming.
A.3

Changing the IP address during runtime

Changing the IP address during runtime
You can change the following address parameters of the CP at runtime controlled by the
program:
● IP address
● Subnet mask
● Router address
Apart from the address parameters of the CP, with T_CONFIG the address parameters of
DNS servers (IF_CONF_DNS) and NTP servers (IF_CONF_NTP) can also be changed
program controlled.
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
OUC program blocks (CP)
A.3 Changing the IP address during runtime
159