Status
84xx
8500
8501
8502
8535
8550
8554
85xx
4.7

Maintenance

Maintenance functions
You can find a description of the following maintenance functions in the manual of the
respective module, see Bibliography (Page 187).
● Firmware update
● Reset
● Module replacement
See also
WBM of the TIM 1531 IRC (Page 167)
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
Meaning
Other error message from the e-mail server
Apart from the leading "8", the message corresponds to the three-digit error number of the
SMTP protocol.
Syntax error: Command unknown.
This also includes the error of having a command chain that is too long. The cause may be
that the e-mail server does not support the LOGIN authentication method.
Try sending e-mails without authentication (no user name).
Syntax error. Check the following configuration data:
Alarm configuration > E-mail data (Content):
Recipient address ("To" or "Cc").
Syntax error. Check the following configuration data:
Alarm configuration > E-mail data (Content):
Email address (sender)
SMTP authentication incomplete. Check the "User name" and "Password" parameters in
the configuration.
SMTP server cannot be reached. You have no access rights. Check the following configu-
ration data:
Module configuration > E-mail configuration:
User name
Password
Email address (sender)
Alarm configuration > E-mail data (Content):
Recipient address ("To" or "Cc").
Transfer failed
Other error message from the e-mail server
Apart from the leading "8", the message corresponds to the three-digit error number of the
SMTP protocol.
Diagnostics
4.7 Maintenance