Delete invalid or redundant connections
If there are unauthorized or unwanted redundant connections, you must delete a connection
path:
1. In the "Configured connection paths" table, select the unwanted connection path.
2. Click "Delete" in the shortcut menu.
3.19.3

Specifying connection paths

Rules for connection configuration
Note the following rules for connection configuration:
● Connections can be configured for the following networks:
– Connections in Ethernet networks between TIM modules and CPs
– Connections in classic WAN networks (dedicated line/dialup network) - only between
● You can create connections between endpoints (subscribers) that are configured in the
STEP 7 project.
Fields are available in the connection table for the address data and interface parameters
of both endpoints.
● The endpoint of a connection is always the CPU, not the communications module.
Exception: Third-party device (see below)
● A connection segment must be created for the way there and the way back for each
connection.
Example of a connection between Partner 1 and 2:
– Connection segment 1 ⇒ 2
– Connection segment 2 ⇒ 1
● A connection must run over a single subnet.
● You can create connections between an endpoint of the STEP 7 project and a "third-party
device" that is not configured in STEP 7. The third-party device is located in another
subnet and can be reached via a network gateway.
In this case, configure the network gateway as an endpoint of the connection.
● You can configure single and redundant connections between two subscribers.
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
TIM modules
Configuration
3.19 Telecontrol connections
89