Specifications Of Electrical Parts - Toshiba RAV-GM1101AT8P-E Service Manual

Outdoor unit digital r32 inverter
Hide thumbs Also See for RAV-GM1101AT8P-E:
Table of Contents

Advertisement

5. SPECIFICATIONS OF ELECTRICAL PARTS

Outdoor Unit
No.
Parts name
1
Compressor
2
Outdoor fan motor
3
High pressure switch
4
PMV-Coil
5
Coil-value-4way
6
Reactor
P.C.board for control and fan motor drive
7
8
P.C.board for compressor drive
9
Outdoor temp. sensor (TO sensor)
10
Discharge temp. sensor (TD sensor)
11
Suction temp. sensor (TS sensor)
Heat exchanger sensor (TE sensor)
12
13
Heat exchanger sensor (TL sensor)
14
Fuse (Mounted on P.C.board, MCC-1626)
15
Fuse (Mounted on P.C.board, MCC-1626)
16
Fuse (Mounted on P.C.board, MCC-1626)
17
Fuse (Mounted on P.C.board, MCC-1627)
Fuse (Mounted on P.C.board, MCC-1627)
18
19
PTC Thermistor
Type
RX330A2T-20M
WDF-340-A100-1
ACB-4UB83W
CAM-MD12TCTH-7
STF-H01AJ1872A1
CH-55-2Z-T
MCC-1626
MCC-1627
50T 100H
FJL 250V 6.3A
SCT 3.15A
50T(P) 063HFGF-001C4
GAC1 31.5A
MZ32-101RMARD01E
- 25 -
FILE NO.SVM-18044
Specifications
Output 3000W
Output 100W
ON : 3.2MPa, OFF : 4.15MPa
DC12V
AC220V ~ 240V
5.4~6.14mH, 14A
10 kΩ at 25°C
50 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
T10A, 250V
T6.3A, 250V
3.15A, 250V
T6.3A, 250V
31.5A, 500V
100Ω, 500V

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents