Toshiba RAV-GM1101AT8P-E Service Manual page 51

Outdoor unit digital r32 inverter
Hide thumbs Also See for RAV-GM1101AT8P-E:
Table of Contents

Advertisement

Contents Error Display
* When fixations of the errors were overlapped, the latest error is displayed.
ITEM
No.
1
Normal
2
Discharge temperature sensor (TD) error
3
Heat exchanger temperature sensor (TE) error
4
Heat exchanger temperature sensor (TL) error
5
Outside air temperature sensor (TO) error
6
Suction temperature sensor (TS) error
7
Heat sink temperature sensor (TH) error
8
Heat exchanger sensor (TE, TS) connecting error
9
EEPROM error
10
Compressor breakdown
11
Compressor lock
12
Current detection circuit error
13
Thermostat for compressor activated
14
Model data not set
15
MCU-MCU commumication error
16
Discharge temperature error
17
High pressure SW error
18
Power supply voltage error
19
Heat sink overheating error
20
Gas leak detected
21
4-way valve reverse error
22
High pressure release operation
23
Fan system error
24
Short-circuit of compressor drive element
25
Position detection circuit error
26
Compressor IPDU or other (not specially identifi ed)
27
Power supply error
: ON
: OFF
: Rapid flash (5 times /sec.)
* The LEDs are located at the top right of the P.C.
board of the outdoor unit as shown in the figure on
the right.
Check code
[Wired remote
D800
D801
controller]
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow)
F04
F06
F07
F08
F12
F13
F15
F31
H01
H02
H03
H04
L10
L29
P03
P04
P05
P07
P15
P19
P20
P22
P26
P29
-
-
- 51 -
FILE NO.SVM-18044-1
LED Display
D802
D803
D804
D805
(Green)
Inspection window
through which to
check the LED
displays
Electric parts cover

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents