Installation; Line-Side Connection - Siemens SIMATIC ET200SP PS 6EP7133-6AB00-0BN0 24 V/5 A Manual

System power supply
Table of Contents

Advertisement

Installation

Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1

Line-side connection

SIMATIC ET200SP PS power supplies are designed for connection to a 1-phase AC line
supply (TN or TT system according to IEC 60364-1) with a rated voltage of 120/230 V AC,
50/60 Hz.
Figure 5-1
The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line supply
connection (Page 23)), and must be implemented according to IEC 60364 . A protective
device (miniature circuit-breaker or circuit-breaker) and a disconnection unit for the power
supply must be provided. A ground-fault circuit interrupter is not permissible against indirect
contact as the only protective measure. This is true for the complete line supply protected by
the ground-fault circuit interrupter.
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434
WARNING
Line supply connection
5
23

Hide quick links:

Advertisement

Table of Contents
loading