Technical data
6.2 Output
Duration of the overload capability
for an overcurrent condition caused
by a short circuit in operation.
Remark
Can be connected in parallel to
increase the power rating
Number of devices that can be
connected in parallel to increase
the power rating, units
Output characteristic
Capacitive load, max.
Figure 6-2
Figure 6-3
30
6EP7133-6AB00-0BN0 (24 V/5 A)
100 ms
once-only
Yes
2
see Figure 6-3 Output characteristic
6EP7133-6AB00-0BN0 (Page 30)
2 mF/A
Startup delay/voltage rise
Output characteristic 6EP7133-6AB00-0BN0
6EP7133-6AE00-0BN0 (24 V/10 A)
100 ms
once-only
Yes
2
see Figure 6-4 Output characteristic
6EP7133-6AE00-0BN0 (Page 31)
2 mF/A
SIMATIC ET200SP PS