Tripp Lite SmartOnline SU3000RTXL2U Owner's Manual page 17

Rack/tower on-line ups system
Hide thumbs Also See for SmartOnline SU3000RTXL2U:
Table of Contents

Advertisement

Available languages

Available languages

5. Operation
CONFIGURATION
Property
Min. Batt. to
Restart
Low Batt. Alert
Timed Shutdown
Timed Shutdown
Shutdown
Completion
DB9 Settings
(Output pins 1&5)
DB9 Settings
(Output pins 8&5)
17-04-276 9335AA.indb 17
DEVICE SETTINGS
Value(s)
• Enter: 10-90%
• Disable (factory setting)
• Enter: 10-90%
(factory setting is 20%)
• Enter a time interval (mm:ss)
• Enable/Disable (factory setting)
• Required (factory setting)
• Interrupt OK
• On battery (factory setting)
• On bypass
• Output on
• Low battery
• On battery
• On bypass
• Output on
• Low battery (factory setting)
DEVICE PROPERTIES
Description
Minimum battery charge level
to restart forces the UPS to wait
until batteries have recharged to
the selected percentage before
automatically restarting.
Note: UPS can be manually started using
the power button if battery is below the
minimum battery restart threshold.
Requires Auto-Restart be enabled
when power is restored.
Enables the UPS to send a low-
battery alert as batteries discharge
to the selected charge level during a
power failure.
Timed Shutdown sets the maximum
amount of battery runtime in seconds
or minutes the UPS will provide during
a power failure.
Use the DISABLE setting for the
longest possible battery runtime.
The UPS will communicate shutdown
messaging to connected systems
prior to UPS shutdown. The setting of
INTERRUPT OK will interrupt shutdown
messaging if power is restored after
shutdown messaging is sent.
The UPS will signal the selected
condition by shorting pins 1&5 on the
DB9 port.
The UPS will signal the selected
condition by shorting pins 8&5 on the
DB9 port.
17
5/1/2017 1:24:51 PM