5. Operation
AC Outlets: These outlets provide connected equipment with pure sine
wave AC output derived from the AC line during normal operation and
derived from battery power during blackouts and severe brownouts or
overvoltages. Output power is filtered to protect connected equipment
against damaging surges and line noise.
The outlets are divided into numbered load banks, as labelled on the unit.
NEMA L5-30R
Using PowerAlert software and cabling or an optional WEBCARDLX, load
banks may be individually turned off and on from a remote location,
allowing users to reset or reboot connected equipment.
NEMA 5-15/20R
CONTROLLABLE LOAD 1
CONTROLLABLE LOAD 2

5.6 Communications

Communication Ports (USB and RS232): These ports connect the UPS
system to a computer. Use with Tripp Lite's PowerAlert software and
included cabling to allow the computer to automatically save open files and
shut down during a blackout. Also use PowerAlert software to control UPS
system load banks and monitor a wide variety of AC line power and UPS
USB
system operating conditions. See Section 4.4: Optional Connections for
cable connection instructions. Refer to the PowerAlert documentation for
software installation instructions.
The RS232 port may also be used as a contact closure port. The port's
numbered pin assignments are shown in the RS232 (DB9) illustration at
left. See DB9 Settings in Section 5.8: Configuration Options via
RS232 (DB9)
WEBCARDLX for a full list of DB9 features.
EPO (Emergency Power Off) Port: The UPS system has an EPO port that
may be used to connect the UPS system to a contact closure switch to
enable emergency UPS system shutdown. See Section 4.4: Optional
Connections for more information. After re-connecting to utility power, see
Section 4.3: Connection and Start-Up for start-up instructions.
Battery Pack Configuration Port: For external batteries with
communication built-in, plugging the battery communication cable into this
port allows the UPS to automatically detect the external battery. This wired
data connection enables automatic detection and configuration for up to 6
SMART Battery Packs to the UPS.
14