Power Transformer Wiring; Carrier Network Communication Bus Wiring; Mounting; Connection To The Communication Bus - Carrier 33PILOT-01 Installation And Operation Instructions Manual

System pilot
Hide thumbs Also See for 33PILOT-01:
Table of Contents

Advertisement

Power Transformer
Wiring
--
An
individual,
field-
supplied, 24 vac power transformer
is highly recommended
for
each System
Pilot. Transformers
must be UL Class 2 rated.
Standard
applications
require a 24 vac transfonnel:
rated at
40 va typic_d. All transformer
secon&uies
are required
to be
grounded.
Use only stranded copper conductors
for _dl wiring
to the System Pilot.
Wiring connections
must be made in accor&mce
with NEC
(National Electric_d Code) and local codes. Ground one side of
the transformer
secondary
at the transformer
location. Connect
the system
ground
of the transformer
to the System
Pilot
terminal
JPI-I
(GND).
Connect
the 24 VAC-
side of the
transformer
to the System
Pilot terminal
JP1-2 (24 VAC-).
Connect
the 24 VAC+
live side of the transformer
to the
System Pilot terminal JP1-3 (24 VAC+). See Fig. 1. The power
supply is 24 vac at 60 Hz _+15%, 10 va minimum.
NOTE:
Do not run sensor
or communication
wiring in the
same conduit
with line-voltage
wiring.
Do not run 24-vac
wiring
in the same multi-conductor
cable used for sensors
or communications.
Perform
the
following
steps
to
connect
the
power
transformer:
1. Install
the field-supplied
transformer
in an electrical
enclosure
that conforms
to NEC and local codes.
2. Connect
24 vac from the transformer
as shown in the
wiring
diagram
(Fig.
1). Be sure to observe
polarity
when connecting
the transformer
power. The grounded
terminal
must be connected
to the transformer
ground
terminal
as shown.
If the system pilot is powered
with the salne transformer
as the other devices, be sure that polarity is maintained
and that adequate power is available for all devices. Never
power
half-wave
and
lull-wave
devices
on the same
transformer
or &_mage may occur to one or both devices.
Carrier
Network
Communication
Bus Wiring --
The System Pilot connects to the bus in a daisy chain ammge-
ment. The System Pilot may be installed on a primary C;urier
communication
bus or on a local bus wired to a VVT Zone
Controller's
COMM2
port. When many System Pilots _ue used,
connecting
to a loc_d bus is recommended.
See Fig. 2 for local
bus wiring to a zone controllel:
At tiny baud (9600,
19200, 38400 baud), the number
of
controllers
is limited to 128 zones maximum.
Bus length may
not exceed 4000 1l, with no more than 60 total devices on any
1000-ft
section.
Optically
isolated
RS-485
repeaters
_ue
required every 1000 ft.
The fiLst device in a netwoN
connects directly to the bridge
and the others ;ue wired sequenti_dly in a daisy chain fashion.
Refer to Fig. 3 for an illustration
of Cturier Communication
Bus wiring.
COMMUNICATION
BUS
WIRE
SPECIFICATIONS
--
The communication
bus wiring
is field-supplied
and field-
installed.
It consists
of shielded
three-conductor
cable with
drain (ground)
wire. The cable selected
must be identic_d to
the communication
bus wire used for the entire network.
See
Table 1 for recommended
cable.
Table 1 -- Recommended
Cables
MANUFACTURER
CABLE
PART NO.
Alpha
2413 or 8463
American
A22503
Belden
8772
Columbia
02525
NOTE: Conductors
and drain wire must be at least 20 AWG (American
Wire
Gage), stranded,
and tinned copper. Individual
conductors
must be insulated
with PVC, PVC/nylen,
vinyl, Teflon, or polyethylene,
An aluminum/polyester
100% foil shield and an outer jacket
of PVC, PVC/nylon,
chrome vinyl, or
Teflon
with a minimum
operating
temperature
range of -20
C to 60 C is
required.
CONNECTION
TO THE COMMUNICATION
BUS
1. Strip the ends of the red, white, and black conductors
of the communication
bus cable.
2. Connect
one end of the communication
bus cable to
the communication
port labeled
COMM2
(if connect-
ing on a local bus).
When
connecting
the communication
bus
cable,
a
color
code
system
for the entire
network
is recom-
mended
to simplify
installation
and
checkout.
See
Table 2 for the recommended
color code.
Table 2 -- Color Code Recommendations
CON BUS WIRE
SIGNAL TYPE
COLOR
+
Red
Ground
White
Black
PLUG PIN
NUMBER
6
5
4
3. Connect
the other end of the communication
bus cable
to the terminal
block labeled Carrier Network
Connec-
tion on the System
Pilot.
See Fig. 1. Following
the
color
code in Table
2, connect
the Red (+) wire to
Terminal
JPI-6
(CCN+).
Connect
the White
(ground)
wire
to Terminal
JPI-5
(CCN
GND).
Connect
the
Black
(-) wire
to Terminal
JPI-4
(Carrier
Network
Connection
-).
4. If connecting
to a Carrier communicating
network
bus,
connect
additional
devices
in a daisy
chain
fashion,
following
the color
coded wiring
scheme
in Table 2.
Refer to Fig. 3.
NOTE:
The communication
bus drain wires
(shield)
must
be tied together
at each device.
If the communication
bus is
entirely
within one building,
the resulting
continuous
shield
must be connected
to ground at only one single point. If the
communication
bus cable exits from one building and enters
another
building,
connect
the shields
to ground
at a light-
ning suppressor
in each building
where
the cable enters
or
exits (one point only).
Mounting
--
There are two options for mounting
the Sys-
tem Pilot to the w_dl, recess mounting or surface mounting. The
System Pilot will snap together with either the Recess Mount
or the Surface Mount backpkite.
NOTE:
The
recess
mount
backplate
is provided
with the
System
Pilot.
RECESS
MOUNT--This
provides
the thinnest
mounting
configuration
(See Fig.
4). The
backplate
containing
the
recessed terminal block can be mounted directly to the wall by
cutting a hole 13/4-in. wide by 21/8-in. high. Mark location and
cut hole in wall. Ensure the System Pilot location is acceptable
before cutting tiny holes in wall.
SURFACE
MOUNT
-- This provides surface mounting
con-
figuration, which allows use of a small hole in the wall. Surface
mount backplates
may be purchased
separately.
(See Fig. 5.)
Attach backpkite
and the assembly
will mount directly to the
wall, requiring
only a small hole in the wall _dlowing the wiring
connection
to pass through.
Once the System Pilot is secured to wall with the backplate
assembly
(snapped
together),
care
must
be taken
not to
bend or break the interlocking
tabs when removing.
Gently
remove
System
Pilot by rocking
up/down
until interlocking
tabs release.
DECORATIVE
BEZEL-
A decorative
bezel may be pur-
chased separately
in boxes of 10. See Fig. 6. The bezel can be
used to hide any marks/screw
holes left from the previous
thermostat.
This decorative
bezel can be used in either the
recess or surface mount installation
by snapping it onto back of
recessed
mount backplate
or surface mount backplate
before
securing to wall.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents