Remote Attach Configuration (Remote) Table; Holiday (Holdyxxs) Configuration Table - Carrier 33PILOT-01 Installation And Operation Instructions Manual

System pilot
Hide thumbs Also See for 33PILOT-01:
Table of Contents

Advertisement

Table 3 -- Alarm Configuration
(ALARMDEF)
DESCRIPTION
DISPLAY
POINT
RANGE
Alarm Configuration
Re-alarm Time
xxx min
RETIME
0-1440
Alarm Routing
xxxxxxxx*
ROUTING
0-11111111
*This is an 8-bit binary value, where each digit is 0 or 1.
DEFAULT
0
00000000
Table
4-
Broadcast
Configuration
(BRODEF)
DISPLAY
POINT
RANGE
DEFAULT
DESCRIPTION
Real Time Clock
Time Broadcast Enable
Daylight Savings
Start Month
Start Day of Week
Start Week
Start Time
Start Advance
Stop Month
Stop Day of Week
Stop Week
Stop Time
Stop Back
Disable/Enable
XX
X
X
XX:XX
XXX min
XX
X
X
XX:XX
XXX rain
TIMEBCST
DAYSAV
DLSTRMON
DLSTRDOW
DLSTRWK
DLSTRTIM
DLSTRADV
DLSTPMON
DLSTPDOW
DLSTPWK
DLSTPTIM
DLSTPADV
0-1
1-12
1-7
1-5
0:00-24:00
0-360
1-12
1-7
1-5
0:00-24:00
0-360
Disable
4
7
1
2:00
6O
10
7
5
2:00
6O
Start Time --
Use this decision
to enter the time of day at
which the real time clock will adjust the time for the start of
daylight saving time.
Start Time:
Allowable
Entries 0:00 to 24:00
Default Value
2:00
Start Advance
--
Use this decision
to enter the number
of
minutes by which the real time clock will adjust the time for
the start of daylight saving time. An entry of 0 will disable this
feature.
Start Advance:
Allowable
Entries 0 to 360 min
Default Value
60 min
Stop Month
-- Use this decision to enter the month in which
the real time clock will adjust the time for the end of daylight
saving time.
Stop Month:
Allowable
Entries 1 to 12
Default Value
10
Stop Day of Week -- Use this decision to enter the day of the
week on which the real time clock will adjust the time for the
end of &_ylight saving time.
Stop Day of
WEek:
Allowable
Entries 1 to 7
Default Value
7
Stop Week -- Use this decision to enter the week of the month
in which the real time clock will adjust the time for the end of
daylight saving time.
Stop Week:
Allowable
Entries 1 to 5
Default Value
5
Stop Time --
Use this decision
to enter the time of day at
which the real time clock will adjust the time for the end of
daylight saving time.
Stop Time:
Allowable
Entries 0:00 to 24:00
Default Value
2:00
Stop Back -- Use this decision to enter the number of minutes
by which the real time clock will adjust the time for the end of
daylight saving time. An entry of 0 will disable this feature.
Stop Back:
Allowable
Entries 0 to 360 min
Default Value
60 min
Holiday
(HOLDYxxS)
Configuration
Table -- The
Holiday
Configuration
Table is shown in Table 5. Up to 30
Holiday tables (HOLDY01S
- HOLDY30S)
may be config-
ured. An explanation
of each configuration
decision follows.
START
MONTH
-- Use this decision to indicate the month
of the year in which the holiday will begin.
Start Month:
Allowable
Entries 1 to 12
Default Value
1
START
DAY -- Use this decision to indicate the day of the
month on which the holiday will begin.
Start Day:
Allowable
Entries 1 to 31
Default Value
1
DURATION
-- Use this decision to indicate the number
of
consecutive
&Lys that the holiday will last. If you enter 0 in this
decision, the holiday schedule will be disabled.
Duration:
Allowable
Entries 0 = Disable or 1 to 365
Default Value
0
Remote
Attach
Configuration
(REMOTE)
Table
--
The Remote Attach Configuration
Table is shown
in Table 6. An explanation
of each configuration
decision
follows.
REMOTE
ATTACH
ENABLE
-- Use this decision to enable
the Remote Attach
iimction. This function allows the System
Pilot to perform the following operations
for a specified device
referred to as the "remote device." This limctionality
occurs as
a background
task to the System Pilot's normal functionality.
write space temperature
compute
an operating
mode
monitor
and modify set points
While
the Remote Attach function
is enabled,
the System
Pilot can attach to (using the Progrmn screen Attach option)
and communicate
with the remote device or any other device.
The Remote Attach will remain in effect until it is disabled.
Space temperature
will be written to the remote device once
a minute or whenever
the value changes by 0.3 E If a Remote
Attach is disabled, the System Pilot will auto the space temper-
ature variable in the remote device.
NOTE:
If Remote
Attach is being used with a VVT®
zone
controllel: the System Pilot will write its space tempemtme
to
the Zone Controllel: but will not perform the set point monitor-
ing/control
or mode calculation.
Set point monitoring/control
and mode calculation
is performed
for the Zone
Controller
from the Zone Controller Default Screen.
Remote Attach:
Allowable
Entries Disable / Enable
Default Value
Disable
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents