Trane THS04 User Manual page 7

Wall thermostat

Advertisement

Active setpoint
display
Home
Screen
Figure 8
The temperature setpoint override command will remain active until Occupancy override timer expires. It is
possible to edit the override timer under PGD1: Setting-THS04: Occupancy Override timer  60 minutes
(default value). If Occupancy Override timer value is set at zero, it will disable the timer function and let
modified setpoint unchanged if no other actions are performed on button 5 (Figure 4).
Note : The amount of offset applied to the active setpoint is also applied to the opposite mode setpoint. For
instance, an offset of +1.5K on Heating setpoint (Active Heating setpoint 20°C 21.5°C) will move the
cooling setpoint with the same magnitude (Active Cooling setpoint 24°C 25.5°C)
7. Real time clock adjustment
It is possible to adjust the controller time and date under PGD1: Setting- Clock and password: Time and
Date settings.
Version History
Oct-2017: Simplify default level and remove password to change mode, occupancy and setpoint .
Implementation started with CH536 release 1.52.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating
and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC
systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2016 Trane All rights reserved
RT-SVU010B-GB_1217
supersedes RLC-SVU010A_1116
Active setpoint
temporary override
+ Wait
3s

Advertisement

loading