12. Press Previous Menu button and navigate to "HOME"
screen and allow test to finish. The display similar to
the one at the right will be displayed after "SYSTEM
TEST" completes. Test is complete only when "CODE
11" notice clears from BOTH the thermostat display
AND the seven segment LED display on the outdoor
unit. Please wait for test to complete and for both codes
to clear.
s
4. s
t
teP
et
heRmostat to
If required additional charging amount cannot be charged to
the system without operation, then use this "CHARGE MODE".
Please follow the following sequence to enter CHARGE
MODE.
CHARGE MODE allows for charging of the system. System
operates for a duration of approximately one hour while the
equipment runs at full capacity. After one hour, the CHARGE
MODE ends and the system resumes normal thermostat
operation.
Before starting the CHARGE MODE, turn off the electric
heater.
1. On the "HOME" screen, select "MENU".
NOTE: Ensure the thermostat is in OFF. Select
"SYSTEM" menu. Choose "OFF" before "CHARGE
MODE".
2. From the "MENU" screen, select "ComfortNet User
Menu".
ChaRge mode
Sun
2018
Sun
2018
17
17