SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION

FIGURE 7 - SYSTEM SCREEN

The System Screen provides a general overview of
common chiller parameters for both shells.
DISPLAY ONLY FIELDS
FIELD/LED NAME
Discharge Temperature
Input % Full Load Amps
Input Current Limit Setpoint
Condenser Liquid Temperature - En-
tering
Condenser Liquid Temperature - Leav-
ing
Chilled Liquid Temperature - Entering
Chilled Liquid Temperature - Leaving
Chilled Liquid Temperature - Setpoint
Head Pressure
Head Pressure Setpoint
Condenser Pressure
32
DISPLAY ONLY FIELDS
Displays the temperature of the refrigerant in its gaseous state at discharge of
the compressor as it travels to the condenser.
This displays the percentage of full load amps utilized by the system.
Displays the current limit value in use. This value is percent of Input Full Load
Amps.
Displays the temperature of the liquid as it enters the condenser.
Displays the temperature of the liquid as it leaves the condenser.
Displays the temperature of the liquid as it enters the evaporator.
Displays the temperature of the liquid as it leaves the evaporator.
Displays the programmed temperature setpoint for leaving chilled liquid. It is the
local value or remote reset value depending on control source.
Displays the pressure difference between the condenser and evaporator
(condenser minus evaporator). Only appears when Head Pressure Control is
enabled
Displays the active Head Pressure Setpoint to which the head pressure is being
controlled. Only appears when Head Pressure Control is enabled
Displays the refrigerant pressure in the condenser.
LD26729
DESCRIPTION
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
JOHNSON CONTROLS