Removal of Coils / Thermistors

8. Removal of Coils / Thermistors
Procedure
Step
1
Remove the screw of
the four way valve coil.
2
Remove the screw and
remove the defrost
solenoid valve coil.
Remove the electronic
3
expansion valve coil for
each room.
4
Release the fixture and
remove the discharge
pipe thermistor.
22
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Electronic
expansion
valve coil
Fixture
Discharge pipe
thermistor
Four way
valve coil
(R2194)
Only for the U.S. model
Defrost
solenoid
valve coil
(R2195)
(R2196)
Place the thermistor so that
its end comes up to the end
of the fixture.
Be careful not to lose the
fixture for the discharge pipe
thermistor.
Thermistor
Pipe
(R10367)
Si121175
Points
Fixture
(R10536)
Removal Procedure