Parameter reference
8.7 Maintenance and Diagnostics (3.)
mA input (3.2.8.19.)
Displays the mA input value.
Index
Related
8.7.2.9

Pump records (3.2.9.)

Identifies pump usage and if the associated Relay Function [Relay Function (2.8.1.4.)
(Page 195)] is set for any pump control feature. The value is that of the pump connected to
the associated terminals.
Enter a value to set the current record to that value. Use this if a pump is added with a
known number of hours logged, or the value can be reset to 0 after maintenance.
Relay selector (3.2.9.1.)
Sets the relay index for all parameters applicable to this sub-menu.
Pump hours (3.2.9.2.)
Sets or shows the total running time of the selected relay, in hours.
Range: 0 ... 999999
Pump run time (3.2.9.3.)
Sets or shows the total running time of the selected relay, in hours.
Range: 0 ... 999999
Pump starts (3.2.9.4.)
Shows or resets the accumulated number of times the selected relay has been ON.
Index
Values
Related
To change the relay assignment, see Relay selector (3.2.9.1.) (Page 260).
Pump run-ONs (3.2.9.5.)
Shows or resets the accumulated number of times the selected relay has been held ON via
Run-ON Interval (2.8.2.7.1.) (Page 205).
Index
Values
Related
260
mA Input
Range: 0.000 ... 24.00 mA
Relay
Range: 0 ... 9999
Relay function (2.8.1.4.) (Page 195)
Relay
Range: 0 ... 9999
Relay function (2.8.1.4.) (Page 195)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC