8.6.6.4

mA Damp Filter (2.6.4.)

Shows the time constant used in the mA input filter to dampen signal fluctuations.
Index
Values
This number is used in the damping calculations. Larger values damp more than smaller
values and 0 disables the signal filter.
8.6.6.5

Scaled mA input value (2.6.5.)

Shows the resulting level value after scaling.
Index
Values
8.6.6.6

Raw mA input value (2.6.6.)

Shows the raw mA input supplied by an external device.
Index
Values
8.6.7

Volume (2.7.)

Carries out a volume conversion from a Level measurement.
8.6.7.1

Level selector (2.7.1.)

Sets the Level Point index for all parameters applicable to this sub-menu.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Global
Range: 0 ... 9999 seconds
Preset: 1 second
Global
Range: -999 ... 9999% (read only)
Preset: calculated from the input mA signal
mA Input
Range: 0.000 ... 20.00 (Read only)
Parameter reference
8.6 Setup (2.)
185