8.6.5.10

Fail-safe mode (2.5.10.)

Use for fail-safe operation, independent of the Material Level (2.4.5.) (Page 178).
Index
Options
Related
8.6.5.11

4 mA output trim (2.5.11.)

Calibrates the 4 mA output
Index
Values
Related
Adjust this value so the device indicates 4.00 mA when 4 mA Output Trim (2.5.11.) is
accessed.
Trimming the 4 mA value:
1. Go to Milliamp Output (2.5.9.) (Page 182) and enter 4.00 mA.
2. Read the value indicated on the current meter or other connected device, and enter it in
mA output trim (2.5.11.)
The new trimmed value will be shown in the current meter or other connected device.
8.6.5.12

20 mA output trim (2.5.12.)

Calibrates the 20 mA output
Index
Values
Related
Adjust this value so the device indicates 20.00 mA when 20 mA output trim (2.5.12.) is
accessed
Trimming the 20 mA value:
1. Go to Milliamp Output (2.5.9.) (Page 182) and enter 20.00 mA.
2. Read the value indicated on the current meter or other connected device, and enter it in
mA output trim (2.5.12.)
The new trimmed value will be shown in the current meter or other connected device.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
mA output
*OFF
mA output responds to Material Level (2.4.5.) (Page 178)
HI
Produce the Span mA output immediately.
LO
Produce the Empty mA output immediately.
Hold
Last known value is held until normal operation resumes.
Value
mA output goes to user-selected value defined in mA Fail-
safe Value (2.4.9.) (Page 180).
Current output function (2.5.3.) (Page 181)
mA Output
Preset: 4.00
20 mA output trim (2.5.12.) (Page 183)
mA Output
Preset: 20.00
4 mA Output Trim (2.5.11.) (Page 183)
Parameter reference
8.6 Setup (2.)
183