Carrier 19XL series Installation Instructions Manual page 36

50/60 hz hermetic centrifugal liquid chillers with hcfc–22 and hfc–134a
Table of Contents

Advertisement

Note: Conductors and drain wire must be 20 AWG (American Wire Gauge) minimum stranded,
tinned copper. Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon,
or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/
nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -4 F to 140 F
(-20 C to 60 C) is required. See table below for cables that meet the requirements.
Manufacturer
Alpha
American
Belden
Columbia
When connecting the CCN communication bus to a system element, a color code system for
the entire network is recommended to simplify installation and checkout. The following color code
is recommended:
Signal Type
+
Ground
CCN Bus Conductor Insulation Color
Red
White
Black
Cable No.
2413 or 5463
A22503
8772
02525
COMM1 Plug PIN No.
1
2
3