Bosch CLIMATE 5000 VRF RDCI Series Installation Manual page 5

All dc inverter outdoor units
Hide thumbs Also See for CLIMATE 5000 VRF RDCI Series:
Table of Contents

Advertisement

290
245
205
R amplification
3) 14HP, 16HP
R
290
245
205
R amplification
4.5 Outdoor Unit Cascade Sequence
A system with one or more outdoor units installed, will need to follow this
method: Outdoor units should be placed from large capacity to small
capacity. The largest should be installed nearest to the first branch joint. You
need to set the largest capacity as the master unit.
1) Place the 16HP at a side of the first branch joint site.
2) Place the unit from the large capacity to the small (See the detail
placement illustration)
3) Set 16HP as the main unit, while the 12HP and the 10HP as the slave
unit.
RDCI Series – All DC Inverter Outdoor Units
High-pressure
gas balance valve
The connective pipe
diameter Ø19.1
Low-pressure gas
side shut-off valve
The connective pipe
diameter Ø25.4
High-pressure gas
side shut-off valve
The connective pipe
diameter Ø19.1
The 1st branch joint
Liquid side
shut-off valve
The connective pipe
diameter Ø15.9
Oil balance valve
For the Cascaded Units
Fig. 4-7
4.6 Installation space for outdoor unit
Fig. 4-8
High-pressure
4.7 Layout
gas balance valve
The connective pipe
diameter Ø19.1
Low-pressure gas
side shut-off valve
The connective pipe
diameter Ø28.6
High-pressure gas
side shut-off valve
The connective pipe
diameter Ø22.2
Liquid side
shut-off valve
The connective pipe
diameter Ø15.9
Oil balance valve
For the Cascaded Units
Fig. 4-9
OUTDOOR UNIT INSTALLATION | 5
16HP
Outdoor unit
(38HP)
SBOX
Indoor unit A
When installing the unit, leave a space for maintenance shown in
Fig.4-12 Install the power supply at the side of the outdoor unit. For
correct installation procedure, read installation manual.
In case there are obstacles surrounding the unit, refer to 4-17.
>1000mm
100mm~500mm
100mm~500mm
>1000mm
>1000mm
Top view of the outdoor unit
When the outdoor unit is higher than the surrounding obstacle
One row
>1m
Front
Front
100-500mm
12HP
10HP
SBOX
SBOX
Indoor unit B
Indoor unit C
Fig. 4-10
>1000mm
Fig. 4-12
Fig. 4-13
6 720 862 437 (2016/10)