Explanation of main board
Table.8-2
No.
1
Discharge temp. Sensor port for inverter compressor A
2
Discharge temp. Sensor port for inverter compressor B
3
Temperature of module sensor port
4
Reserve
Wiring port for communication between indoor and outdoor units, indoor
5
unit network, outdoor unit network and network accounting
6
Three-phase detection port
7
Reserve
8
Power output of transformer No.1
9
Power output of transformer No.2
10
Heat output terminal of the inverter compressor A
11
Heat output terminal of the inverter compressor B
12
Exv A driving port
13
Exv B driving port
14
Four-way valve output terminal
15
One-way valve output terminal
16
Power control output terminal
17
Null line terminal
18
Power output of transformer No.1
19
Power output of transformer No.2
20
Activation port of inverter module B
21
Port for inverter module B voltage inspection
22
Port for inverter module A voltage inspection
23
Activation port of inverter module A
24
Power supply port for main control panel
25
ON/OFF signal input port for system high pressure inspection
26
ON/OFF signal input port for system low pressure inspection
27
Reserve
28
Reserve
29
Current inspection port of the inverter compressors A and B
30
Input port for system high pressure inspection
31
Communication ports between outdoor units
32
Detection port for outdoor ambient temp. and left pipe Temp.
33
Detection port for right pipe Temp.
34
Control port of DC fan B
35
Control port of DC fan A
8.5 Electric parameters of outdoor unit
Table.8-3
System
Voltage
Hz
8HP
380~415
50
10HP
380~415
50
12HP
380~415
50
14HP
380~415
50
16HP
380~415
50
RDCI Series – All DC Inverter Outdoor Units
Content
Outdoor Unit
Min.
Max.
342
440
342
440
342
440
342
440
342
440
Notes:
1. The current value of combination unit is the total value of each basic
model(refer to Table.8-3)
For example: 46HP=14HP+16HP*2
Power current:
MCA=27.9+33.4*2=94.7
TOCA=31.8+32.8*2=97.4
MFA=35+35*2=105
Compressor:
RLA=(17.4+10.5)*3
OFM:
FLA=5.9+5.9*2=17.7
2. RLA is based on the following conditions.
Indoor temp. 27°C DB/19°C WB;Outdoor temp. 35°C DB
3. TOCA means the total value of each OC set.
4. MSC means the Max. current during the starting of compressor.
5. Voltage range
Units are suitable for use on electrical systems where voltage supplied to
unit terminals is not below or above listed range limits.
6. Maximum allowable voltage variation between phase is 2%.
7. Selection wire size based on the larger value of MCA or TOCA.
8. MFA is used to select the circuit breaker and the ground fault circuit
interrupter (earth circuit breaker).
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (kW)
Power Current
MCA
TOCA
MFA
18.4
20.8
25
20.6
22.1
25
21.8
22.8
25
27.9
31.8
25
33.4
32.8
25
ELECTRIC WIRING | 19
Compressor
OFM
MSC
RLA
KW
17.4
16.5
0.42
15.9
17.4
16.5
0.42
15.9
17.4
16.5
0.42
15.9
17.4+10.5
16.5+10.0
0.71
15.9+9.6
17.4+10.5
16.5+10.0
0.71
15.9+9.6
6 720 862 437 (2016/10)