Bosch CLIMATE 5000 VRF RDCI Series Installation Manual page 18

All dc inverter outdoor units
Hide thumbs Also See for CLIMATE 5000 VRF RDCI Series:
Table of Contents

Advertisement

18 | ELECTRIC WIRING
8.4 Dial codes definition
S1 definition
S1
ON
Starting time is set to 10 minutes
S1
Starting time is set to 12 minutes (Default
ON
Factory setting)
S2 definition
S2
Night time selection for 6h/10h
ON
(Default Factory setting)
S2
ON
Night time selection for 6h/12h
S2
ON
Night time selection for 8h/10h
S2
ON
Night time selection for 8h/12h
S3 definition
S3
Night silent mode
ON
(Default the Factory Set)
S3
ON
Silent mode
S3
ON
Super silent mode
S3
ON
None silent mode
S4 definition
S4
Static pressure mode is 0 MPa (Default the
ON
Factory Set)
S4
Static pressure mode is low pressure
ON
(Reserve position, use for customised unit)
S4
Static pressure mode is medium pressure
ON
(Reserve position, use for customised unit)
S4
Static pressure mode is high pressure
ON
(Reserve position, use for customise unit)
6 720 862 437 (2016/10)
S7 definition
S7
ON
Reserve
ENC3 and S12 definition
S12
ENC3
To set the number of indoor units
ON
to 0-15
S12
ENC3
To set the number of indoor units to
ON
16-31
S12
ENC3
To set the number of indoor units to
ON
32-47
S12
ENC3
To set the number of indoor units to
ON
48-63
ENC1 definition
Outdoor unit address
Set the switch to address the unit 0-3
0 Stand for main unit
1-3 Stand for slave uint
ENC2 definition
Outdoor unit capacity setting switch Set the
switch to the correct HP output
For outdoor unit capacity setting
0: 8HP
1: 10HP
2: 12HP
3: 14HP
4: 16HP
S3 definition
Network address setting dial switch Set the
switch to the correct setting
For network address setting
0: system 1
1: system 2
2: system 3
...
7: system 8
RDCI Series – All DC Inverter Outdoor Units