Feed Motor Trouble-Shooting - Quadra-Fire Classic Bay 1200 Service Manual

Insert pellet stove
Hide thumbs Also See for Classic Bay 1200:
Table of Contents

Advertisement

1) TURN ON THERMOSTAT CIRCUIT AND MAKE SURE THAT THE CALL LIGHT IS ON.
2) CHECK FOR POWER AT THE VACUUM SWITCH:
A. IF NO POWER FROM RED WIRE-----CHECK CONTROL BOX OR WIRE HARNESS
B. POWER ON RED BUT NO POWER ON ORANGE-----CHECK VACUUM SWITCH OR VENT SYSTEM
3) CHECK FOR POWER AT THE RED WIRE FROM THE CAPACITOR:
A. IF NO POWER FROM RED WIRE----CHECK WIRE HARNESS OR CONNECTOR PIN
B. IF POWER IS PRESENT-----REPLACE FEED MOTOR OR CHECK CONNECTOR PIN
NOTE: REMEMBER THAT THE FEED CIRCUIT INITIAL FEED TIME IS 1:35. PUSH THE RESET
BUTTON BEFORE EACH TEST.
CAPACITOR JUMPER
WIRE. PART# 230-2150
JUNCTION BOX
4
1
RED
2
5
3
6
WHITE
NOTE: CAPACITOR IS LOCATED IN THE JUNCTION BOX
2-12-2003
CB1200-I PELLET STOVE SERVICE MANUAL

FEED MOTOR TROUBLE-SHOOTING

FEED MOTOR CIRCUIT
CAPACITOR
ACCY
JUMPER
ORANGE
RED/WHITE
*
RED
WHITE
RED
VACUUM
SWITCH
*Color will be black for SN 505324 & above.
PAGE 6
JUMPER IS NEEDED IF
CAPACITOR IN J-BOX
IS BAD OR IF THE
MOTOR NEEDS TO BE
TESTED WITH A TEST
CORD.
RED
BLACK
WHITE
WHITE
FEED MOTOR
250-7700