4.5
Communication ports
Connection of RS232 or USB communication port
Independent
Communication Bay
Any connectivity card
Any connectivity card
1. Connect the RS232
equipment.
2. Connect the other end of the communication cable
port on the UPS.
The UPS can now communicate with EATON power management software.
Installation of the communication cards (optional)
Characteristics of the contact RS232 communication port
Contact characteristics (optocoupler)
•
Voltage: 48 V DC max
•
Current: 25 mA max
614-20306-00 - 9SX 0-6 KVA EMEA_EN
4. Interfaces and Communication
USB
Available
Not in use
or USB
communication cable to the serial or USB port on the computer
17
18
Multiplexed
RS-232
Not in use
Available
or
to the USB
or RS232
17
18
10
It is not necessary to shutdown the UPS
before installing a communication card.
1. Remove the slot cover
screws.
2. Insert the communication card in the
slot.
3. Secure the card cover with the 2 screws.
Pin
Signal
Direction
1
Bat Low
Output
2
TxD
Output
3
RxD
Input
4
I/P SIG
Input
5
GNDS
-
6
PNP
Input
7
8
BAT Mode
Output
9
+5V
Output
communication
9
secured by
2
Function
Low Battery Output
Transmit to external device
Receive from external device
-
Signal Common tied to
chassis
Plug and Play
-
Power supply for external
signal or options
Page 35