Ups Startup Without An External Bypass Switch; 6.3 Startup For Units Installed With An Eaton Bpm Bypass Switch; 6.4 Startup For Units Installed With A Bpe Type Switch; Figure 55. Communication Ports - Eaton 9PXM8S4K User Manual

Table of Contents

Advertisement

6.
Replace the front covers and continue to "

6.3 Startup for Units Installed with an Eaton BPM Bypass Switch

6.4 Startup for Units installed with a BPE Type Switch

6 6 . . 2 2
U U P P S S S S t t a a r r t t u u p p W W i i t t h h o o u u t t a a n n E E x x t t e e r r n n a a l l B B y y p p a a s s s s S S w w i i t t c c h h
To start the UPS unit for the first time after installation:
1.
If external battery cabinets (EBMs) are installed, check the cable connections between the UPS and
external battery cabinets (see ,
2.
Ensure that all power modules and battery modules are properly installed into the UPS cabinet.
3.
If you are using power management software, connect your computer to either the DB9 or USB
communication ports on the top rear panel using the supplied communication cables.

Figure 55. Communication Ports

4.
When starting the UPS, apply input power to the UPS by closing the service circuit breaker:
If external battery cabinets are installed, close the DC emergency disconnect switch button on the
back of each external battery cabinet. Insert the switch key supplied with the cabinet into the button
and turn clockwise 1/2-turn. Pull the button out to close the switch. Turn the key back counter-
clockwise, and remove the key.
5.
The UPS control panel display automatically turns on whenever input power is present and at least one
power module is installed (see ,
6.
Set up the initial operating parameters through the control panel display (see "
6.5 Initial Startup Parameters
7.
If applicable, test proper operation of optional external control signals and computer communication before
connecting the load. (See
8.
If there are receptacles on the UPS rear panel, plug the equipment to be protected into the UPS output
receptacles.
NOTE
9.
Turn on the equipment that is connected to the UPS.
10. If there is an external bypass switch, ensure a proper phase check has been completed then turn the
switch to UPS. Otherwise, close the load distribution circuit breaker(s).
6.2 UPS Startup Without an External Bypass
"5.2 Standard Battery Cabinet Installation
DB9 Port
(CN17)
"6.1 UPS Startup
" ).
"8.5 DB-9 Communication Port
DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10

UPS Startup Without an External Bypass Switch

or
".
or
5.1 Battery Cabinet Options
USB Port
(CN12)
").
" for details.)
Switch,
").
61

Advertisement

Table of Contents
loading

Table of Contents