Xrc G4 Communication Field-Wiring - ABB XSeriesG4 User Manual

Hide thumbs Also See for XSeriesG4:
Table of Contents

Advertisement

G4
XRC
communication field-wiring
G4
The XRC
main electronic board may require some basic setup and wiring.
G4
The standard XRC
enclosure allows the user access to the main electronic board for configuration of jumpers, communication
modules and switches. All user wiring is wired directly to this board.
G4
While the XRC
panel-mount main electronic board(s) are pre-wired inside of the rack mount enclosure to the termination panel
on the rear of the enclosure, it may be necessary to configure some of the jumpers, communication modules and switches that
are located inside of the enclosure on the main electronic board(s).
Communication wiring
Up to two communication ports can be programmed on the XRCG4 board. COMM 0 is the local port required for reading the
XRCG4 with a laptop computer running PCCU32. COMM 1 and COMM 2 can be configured for any combination of RS-232 or
RS-485. See Figure 41 for on-board communications wiring inside the standard XRCG4 enclosure. See
Communications
COMM 2
232 / 485
VBAT
GND
SW - VBAT
OPER
RTS / RRTS
DCD / BUS -
RXD / BUS -
CTS / BUS +
TXD / BUS +
Digital I / O
DO 3
GND
DO 4
GND
DI 3
GND
DI 4
GND
AUXPWR OUTPUT
VBAT
GND
SW - VBAT
GND
To TFIO Modules
( I 2 C Bus Cable )
Figure 42: XRCG4 panel-mount field-wiring diagram, for communication wiring on the rear termination panel of the XRCG4 6990
panel mount enclosure.
XRC # 1
Unit # 1
P 6 B
P 6 A
1
10
18
9
P 8 A
P 8 B
9
1
16
8
P 20
Analog Inputs
P 23
1
1
4
P 18
10
38
Communications
COMM1
232 / 485
VBAT
GND
SW - VBAT
OPER
RTS / RRTS
DCD / BUS -
RXD / BUS -
CTS / BUS +
TXD / BUS +
Digital I / O
DO 1
GND
DO 2
GND
DI 1
GND
DI 2
GND
AI 1
COM
AI 2
COM
AI 3
COM
AI 4
COM
AI 5
COM

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xrcg4 6790Xrcg4 6890Xrcg4 6490Xrcg4 6990