Burner Set-Up Chart - Riello F10 Installation Manual

Oil burners
Table of Contents

Advertisement

SETTING THE AIR ADJUSTMENT
PLATE
A) Regulation
of the combustion
air flow
is made
by adjustment
of the manual
AIR
ADJUSTMENT
PLATE
(1) after
loosening
the FIXING
SCREWS
(2 &3).The
initial
setting
of the
air adjustment
plate
should
be made
according
to Column
5 in the
Burner
Set-up
Chart.
B) The proper
number
on the manual
AIR
ADJUSTMENT
PLATE
(1) should
line up
with the SETTING
INDICATOR
(4) on the
fan
housing
cover.
Once
set, the air ad-
justment
plate should
be secured
in place
by tightening
SCREWS
2 and 3.
C) The final position
of the air adjustment
plate will vary on each installation.
Use in-
struments
to establish
the proper
settings
for maximum
CO 2 and a smoke
reading
of
zero.
NOTE:
Variations
in flue
gas,
smoke,
CO 2
and
temperature
readings
may
be
experienced
when
the burner
cover
is put
in
place.
Therefore,
the
burner
cover
must
be in place
when
making
the final
combustion
instrument
readings,
to
ensure
proper
test results.
®
D5231
BURNER SET-UP CHART
ACTUAL
FIRING
RATE + 5%
GPH
1.45
1.80
2.10
2.40
2.75
2.95
kg/h
4.7
5.8
6.8
7.8
8.9
9.5
NOZZLE
SIZE
GPH
1.25 x 60 °
1.50 x 60 °
1.75 x 60 °
2.00 x 60 °
2.25 x 60 °
2.50 x 60 °
PUMP
PRESSURE
PSI
BAR
145
10
145
10
145
10
145
10
150
10.4
140
9.8
TURBULATOR
SETTING
AIR DAMPER
SETTING
1.5
2.7
2.0
2.8
2.5
3.1
3.5
3.4
4.0
4.2
4.5
4.2
NOZZLES:
Monarch
R-PLP,
DelavanW-B,
DanfossS-B,
SteinenSS-S,
HagoP.
NOTE:
A 60 ° degree
nozzle
is suggested,
however,
a 80 ° degree
nozzle
may be
used
in cases
where
the flame
is unstable
at light-off
when
operated
at low ambient
temperatures.
F10-
12