Wired Wall Thermostat Connection Kit - LG 6RWU0-05A Engineering Product Data Book

Ptac type (60hz/r410a)
Table of Contents

Advertisement

Mechanical accessories

1.2 Wired Wall Thermostat Connection Kit

The PTAC Wire Harness kit provides connection from termi-
nal strip on the PTAC control board to the following board
features:
• Front Desk Control
• Remote Fan (relay must be manufacturer-approved and
have a AC low voltage coil)
• Remote Thermostat (confirm with manufacturer approved).
* If other than a "dry switch" is used in connecting these fea-
tures, consult manufacturer before proceeding.
The PTAC Wire Harness kit contains the following:
1. 7-pin connector for a thermostat connection
• C - Cormmon
• R - 24VAC
• Y - Compressor
• W - E/Heater
• O - Reversing Valve (only on PTHP)
• GH - High Speed Fan
• GL - Low Speed Fan
Note: If there is only one Fan connection(G), connect to
either GH or GL depending on desired fan speed.
Do not wire the thermostat to energize heat pump
and heat strips simultaneously as this will result in
a wiring error.
Figure 1
Wire Nuts (x7)
Wires (x7)
2. 6-pin connector for the following options
• FD1 – Front Desk Control
• FD2 – Front Desk Control
Figure 2
Wire Nuts (x2)
Wires (x2)
67
FD2
FD1
DR2
DR1
MS2
MS1
PTAC
Installation
1. Disconnect power and remove the front panel per unit
installation instruction.
2. Choose the feature desired and insert the proper jumper
wire (included) into the appropriate slot on the housing.
3. Install the appropriate maleconnector header onto the
matching on-board female connector.
4. Connect the kit wiring to the field wiring using the wire
nuts (included). Route the kit wiring as shown in Figure 3.
Do not run wires through basepan or wall
Figure 3