Electrical Characteristics - LG 6RWU0-05A Engineering Product Data Book

Ptac type (60hz/r410a)
Table of Contents

Advertisement

YA Chassis

1.8 Electrical characteristics

Model
UYC073ALEU1(LP073CDUC)
UYC093ALEU1(LP093CDUC)
UYC123ALEU1(LP123CDUC)
UYC153ALEU1(LP153CDUC)
UYH073ALEU1(LP073HDUC)
Y4NZ09ANLD1(LP093HDUC1)
Y4NZ12ANLD1(LP123HDUC1)
UYH153ALEU1(LP153HDUC)
UYC09EALE31(LP096CD3B)
UYC12EALE31(LP126CD3B)
UYH09EALE31(LP096HD3B)
UYH12EALE31(LP126HD3B)
Notes :
1. Voltage range Voltage supplied to the unit terminals should be
within the minimum and maximum range.
2. Maximum allowable voltage unbalance between phase is 2 %.
3. Select wire spec. based on the larger value of MCA.
4. LRA & RLA is measured during each individual compressor test
condition.
5. IFM & OFM is measured at unit test condition.
6. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
43
Unit
Hz
Voltage Voltage range
Min:187
208~230
Max:253
60
Min:239
265
Max:292
PTAC
Power
MCA
MOP
(208 V)
14.5/19.8/28.3
15/20/30
(230 V)
13.6/18.6/26.2
17.9
20
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device (A)
LRA : LRA Locked Rotor Ampere (A)
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor (W)
IFM : Indoor Fan Motor (W)
FLA : Full Load Amperes (A)
6RWU0-05B
Compressor
Moter FLA
RLA
LRA
IFM
OFM
2.9
16.0
3.7
19.0
5.0
27.0
6.55
38.6
2.9
16.0
4.3
26.0
0.36
0.36
4.1
27.0
6.55
38.6
3.3
20.0
4.4
22.0
3.3
20.0
4.4
22.0
Product Data

Advertisement

Table of Contents
loading

Table of Contents