Motor Setpoints Screen; Figure 40 - Motor Setpoints Screen - York YK Style H Operation Manual

With optiview control center centrifugal liquid chillers, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

FORM 160.76-O2
issue date: 6/15/2015

FIGURE 40 - MOTOR SETPOINTS SCREEN

OVERVIEW
This screen allows programming of the winding and
bearing High Temperature Warning/Safety Shutdown
thresholds and the High Vibration Warning/Safety
Shutdown thresholds, along with the vibration input
gain. Also, individual winding temperature sensors can
be disabled on this screen.
DISPLAY ONLY
Motor Windings
Temperature
Displays the Enabled/Disabled status of each winding
sensor. The TEMPERATURE DISABLE Setpoint key
can be used to enable or disable individual winding
temperature sensors. Not shown when Winding Tem-
perature Protection Setpoint on the MOTOR DETAILS
Screen is set to Disabled.
High Winding Temperature Shutdown
Displays the High Winding Temperature safety shut-
down threshold, as programmed with the WINDING
SETUP Setpoint key. Not shown when Winding Tem-
JOHNSON CONTROLS

MOTOR SETPOINTS SCREEN

perature Protection Setpoint on the MOTOR DETAILS
Screen is set to Disabled.
Winding Hotspot Allowance
Displays the Winding Hotspot Allowance temperature.
Not shown when Winding Temperature Protection
Setpoint on the MOTOR DETAILS Screen is set to
Disabled.
Motor Bearings
High Vibration Shutdown
Displays the High Vibration safety shutdown threshold
for the Shaft End and Opposite Shaft End bearings. Not
shown when the Motor Vibration Protection Setpoint
on MOTOR DETAILS Screen is set to Disabled. The
threshold used for this setpoint will either be the val-
ues entered by the Vibration Setup Setpoint or values
derived from the Vibration Baseline Setpoints (refer to
Vibration Setup on Page 116). Also displayed is the
Delay, which is the amount of time the vibration must
exceed the shutdown threshold before the shutdown
occurs.
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
LD10702b
2
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents