Checking The Ionisation And Ignition Electrodes - Wolf CGB-2 Service Instructions Manual

Gas condensing boilers
Table of Contents

Advertisement

Repacing the ignition electrode
Replace ignition electrode with every maintenance.
Check spacings and adapt if not correct.
Replacing the ionisation electrode
Replace ionisation electrode with every maintenance.
Tighten the electrode fixing screws with a torque of
3,0 Nm.!
Carry out a 100 % calibration after working on
the ionisation electrode.
See description HG43 in chapter
"Parameter description" in the installation
instructions.
Fig.: Ignition electrode gap
Fig.: Ionisation electrode gap