Ct/Vt Config - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

Description
Trip Alert
When Enabled the occurance of a Trip will cause the relay to
display the Trip Alert Screen, the only way to leave this screen
is by acknowledging the trip through the TEST/RESET button
on the relay fascia
General Alarm Alert
Relay Identifier
An alphanumeric string shown on the LCD normally used to
identify the relay or the relays purpose
Circuit Identifier
An alphanumeric string shown on the LCD normally used to
identifier the circuit the relay is attached to or the relays
purpose

3.2. CT/VT Config

Description
Phase Nom Voltage
Selects the nominal voltage setting Vn of the voltage input
Phase Voltage Trim Magnitude
Allows trimming of voltage magnitude, the setting value should
be the voltage required to be added to get back to Phase Nom
Voltage.
Phase Voltage Trim Angle
Allows trimming of voltage angle, the setting value is added to
the current voltage angle
Phase Voltage Config
Required to allow for different types of physical VT connections.
Phase VT Ratio Prim
Phase VT Ratio Sec
Vx Nom Voltage
Selects the nominal voltage setting Vn of the voltage input
Vx Voltage Trim Magnitude
Allows trimming of voltage magnitude, the setting value should
be the voltage required to be added to get back to Vx Nom
Voltage.
Vx Voltage Trim Angle
Allows trimming of voltage angle, the setting value is added to
the current voltage angle
Vx VT Ratio Prim
Vx VT Ratio Sec
Phase Current Input
Selects whether 1 or 5 Amp terminals are being used for phase
inputs
Phase CT Ratio Prim
Phase CT ratio to scale primary current instruments
Phase CT Ratio Sec
Phase CT ratio to scale secondary current instruments
Unrestricted ©2018 Siemens Protection Devices Limited
Range
Disabled, Enabled
Disabled, Enabled
(16 Character String)
(16 Character String)
Range
40, 40.1 ... 159.9, 160
-20, -19.9 ... 19.9, 20
-45, -44.9 ... 44.9, 45
Van,Vbn,Vcn, Vab,Vbc,3V0,
Va,Vb,Vc
( 6 Character String)
40, 40.5 ... 159.5, 160
40, 40.1 ... 159.9, 160
-20, -19.9 ... 19.9, 20
-45, -44.9 ... 44.9, 45
( 6 Character String)
40, 40.5 ... 159.5, 160
1, 5
( 6 Character String)
0.2, 0.21 ... 2, 2.1.....7
7SR220 Settings Guide
Default
Enabled
Enabled
ARGUS-M
7SR22
Default
63.5 V
0 V
0 deg
Van,Vbn,Vcn
132000 V
110 V
63.5 V
0 V
0 deg C
132000 V
110 V
1 A
1600 A
1