Siemens Argus 7SR21 Technical Manual page 546

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR210 & 7SR220 Commissioning & Maintenance Guide
2.1.1.1
ANSI Reset
If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected
for an IEC characteristic element, the reset will be instantaneous.
ANSI reset times from operated condition to fully reset are as follows for zero applied current and TM = 1.0. The
reset curve characteristic type and TM is defined by the operating characteristic.
Curve
ANSI-MI
ANSI-VI
ANSI-EI
Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for
the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation
(c) is similar to the first (a) and in line with the expected operate time for the element at this current level.
Repeat the test with the reset time (b) reduced to 50% of the previous value. Ensure that the second operate time
(c) is 50% of the first (a) operate time.
Operate time
Reset time
(expected)
(calculated)
Check correct indication, trip output, alarm contacts, waveform record.
Page 34 of 82
Fully operated to reset with Zero current applied & TM=1 (secs)
Operate time
(measured)
(calculated)
First test (c)
4.85
21.6
29.1
50% Reset
50% operate
Time
time
(calculated)
© 2013 Siemens Protection Devices Limited
50% operate
time
(measured)
Second Test (c)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents