Busbar Vt Fail (60Vtf-Bus) - 7Sr22; Figure 5.2-1 Logic Diagram: Vt Supervision Function (60Vts) - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

60VTS Element
Enabled
Disabled
60VTS Inhibit
60VTS Inhibit
1 or 2 Phase Fail
60VTS
Component
V0
VL1
Phase
V1
VL2
Seq.
Filter
V2
VL3
NPS/ZPS
I0
IL1
Phase
I1
IL2
Seq.
Filter
I2
IL3
I1
I1
V1
60VTS Ext_Trig
60VTS Ext_Reset

Figure 5.2-1 Logic Diagram: VT Supervision Function (60VTS)

5.3
Busbar VT Fail (60VTF-Bus) – 7SR22
When the optional synchronising function is fitted, the synchronising voltage transformer is utilised to provide an
additional monitoring function to check the validity of the measured line and busbar voltages. When the circuit
breaker is closed, both voltages should be either Live or Dead. If the Bus voltage indicates that the VT is Dead
but the corresponding Line voltage is Live, this raises the Bus VT Fail output. A time delay setting is provided to
avoid spurious operations during transient switching conditions. Additionally, this output can be enabled by a
setting, 79 LO Bus VT Fail, to apply a Lockout signal to the autoreclose function so that a sequence will not be
attempted after a trip occurs if it is known that the voltage measurement is not reliable. A similar setting is
available, 79 LO Line VT Fail, which when Enabled will provide a Lockout for a Line VT failure detected by the
60VTS function.
Unrestricted ©2018 Siemens Protection Devices Limited
V Setting
V
>
I Setting
I
<
3 Phase Fail
Ipps Load
>
Ipps
<
Vpps Setting
<
7SR210 & 7SR220 Description of Operation
&
&
> 1
&
&
60VTS Pick-Up
60VTS Delay
&
60VTS Operated
S
Q
60VTS Operated
R
>1
Page 79 of 94