Special Features
Most settings are self-explanatory. The special cases are described in the following
At address 369 VT Con Type, you can specify the connection type of the voltage inputs. If you are using normal
voltage transformers, select CONVENTIONAL.
With 459 Syscon MU Configuration, you can define whether the communication parameter configured with
System configurator or not.
With 461 PhaseIndepRatio, you can specify if the independent CT/VT ratio is supported for each channel.
Under address 700 GOOSE-Stop, you can select whether the GOOSE function of the IEC 61850 protocol is
active or not. If GOOSE-Stop is set to YES, you can release the GOOSE function again via a binary input during
the operation.
Under address 357 SMV-Stop, you can hide the information >SMV-Stop, which controlls the SMV telegram
sending function.

2.1.1.3 Settings

Addr.
104
OSC. FAULT REC.
357
SMV-Stop
369
VT Con Type
459
SysConMUConf
461
PhaseIndepRatio
640
Start image DD
700
GOOSE-Stop

2.1.1.4 Information List

No.
-
>Light on
-
Reset LED
-
DataStop
-
Test mode
-
Feeder gnd
SIPROTEC, 7SC805, Manual
C53000-G1140-C380-1, Release date 05.2014
Parameter
Setting Options
Disabled
Enabled
Yes
No
Conventional
Cap. Volt.Meas.
Enabled
Disabled
Enabled
Disabled
image 1
image 2
image 3
image 4
image 5
image 6
Yes
No
Information
Type of In-
formation
SP
IntSP
IntSP
IntSP
IntSP
Default Setting
Disabled
No
Conventional
Enabled
Disabled
image 1
No
Comments
>Back Light on
Reset LED
Stop data transmission
Test mode
Feeder GROUNDED
Functions
2.1 General
Comments
Oscillographic Fault
Records
SMV-Stop
Voltage Connection Type
MU Configuration via
IEC61850 System Con-
figurator
Phase Independent Ratio
Start image Default
Display
GOOSE-Stop
21