Setting the speed-dependent current limitation for motors with commutation
transition
Converter rated DC current
I
P
A
Current limit
I
3
I
rated
P
rated
P
2
Motor rating plate data
Permissible limit values
I
= 1.4 * I
10
1
I
= 1.2 * I
20
2
The current limitation curve is determined by n
Parameters:
P104 = n
1
P105 = I
(used by unit to calculate I
1
P106 = n
2
P107 = I
(used by unit to calculate I
2
P108 = n
(defines speed normalization)
3
P109 = 0 ... speed-dependent current limitation deactivated
1 ... speed-dependent current limitation activated
Example of a motor rating plate:
*
S H U N T -MOT.
V
46-380
380
ERR.
SEP.
Z: A11 G18 K01 K20
SEP. VENTIL.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
I
10
S1
I
rated
S1
n
n
1
rated
n
E
10
20
1GG5162-0GG4 . -6HU7-Z
NRE
1/MIN
n
n
1
2
50-1490
3400 / 4500
REG.
V
A
310
2.85
77/51 0.87/0.60
Invention point
~1/n (commutation limit curve)
I
3
I
1
I
20
I
2
n
2
n
3
n
= Point at which speed-dependent
E
current limitation intervenes
n
= Maximum operating speed
3
, I
, n
and I
1
10
2
)
)
EN 60034
A
I
I
1
2
78.0-78.5
0.880-26.0
80.0 / 58.0
26.0 / 19.0
THYR.: B6C LV=
0MH 380V/ 50HZ
IP 23
IM B3
I.CL.F
Function descriptions
n
motor
.
20
KW
9-73