Terminal Assignments - Siemens 6RA7086-6KS22 Operating Instructions Manual

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Connections
6.8

Terminal assignments

WARNING
The converter might sustain serious or irreparable damage if connected incorrectly.
The power cables and/or busbars must be secured mechanically outside the converter.
Power section
15A and 30A units
60A to 280A units
400A and 600A units
710A to 850A units
950A to 1200A units
1500A to 2200A units
2200A to 3000A units
The converters are designed for a permanent power supply connection according to DIN VDE 0160
Section 6.5.2.1.
PE conductor connection: Minimum cross-section 10mm
The connection cross-sections must be determined according to the applicable regulations, e.g.
DIN VDE 100 Part 523, DIN VDE 0276 Part 1000.
Function
Armature supply input
PE conductor
Armature circuit motor
connection
Field circuit
15A to 850A units
1200A to 2000A units
2200A to 3000A units
Function
Supply connection
Field winding connection
6-62
Terminal type:
KDS10 PCB feed-through terminal (screw-type terminal)
Maximum cross-section 10mm
1U1,1V1,1W1: Through-hole for M8 (3x20 copper bus)
1C1,1D1: Through-hole for M8 (5x20 copper bus)
1U1,1V1,1W1: Through-hole for M10 (5x30 copper bus)
1C1,1D1: Through-hole for M10 (5x35 copper bus)
Through-hole for M12 (5x60 copper bus)
Through-hole for M12 (10x60 copper bus)
1U1,1V1,1W1: Through-hole for M12 (10x80 copper bus)
1C1,1D1: Through-hole for M12 (10x50 copper bus)
1U1,1V1,1W1: Through-hole for M12 (2x copper bus 10x100)
1C1,1D1: Through-hole for M12 (2x copper bus 10x80)
Terminal
Connection values/Remarks
1U1
1V1
1W1
see technical data in Section 3.4
1C1 (1D1)
1D1 (1C1)
Terminal type:
MKDS terminal block (screw-type terminal)
Maximum connection cross-section 4mm
G10/4 converter terminal (screw-type terminal)
Maximum connection cross-section 10mm
UK16N converter terminal (screw-type terminal)
Maximum connection cross-section 16mm
Terminal
Connection values/Remarks
XF1-2 3U1 2AC 400V (– 20%), 2AC 460V (+10%)
XF1-1 3W1
XF2-2 3C
Rated DC voltage 325V / 373V
XF2-1 3D
For 2AC 400V / 460V supply connection
2
, finely stranded
2
. (see Section 5.1 for connection options).
SIMOREG DC Master
05.05
2
, finely stranded
2
, finely stranded
2
, finely stranded
Siemens AG
6RX1700-0AD76