Parameter list
PNU
Description
U101
Source for the activation of F024 and F020
(2101)
Selection of the binectors that activate fault messages F024 or F020 on
*
log. "1"
S00
0 = Binector B0000
(B115)
1 = Binector B0001
etc.
Up to SW 1.7: F024 (without fault value) if binector = 1 (FB 3)
SW 1.8 and later:
i001:
F024 with fault value 1 (FB 3)
i002:
F024 with fault value 2
i003:
F024 with fault value 3
i004:
F024 with fault value 4
i005:
F020 with fault value 1 (FB 287)
i006:
F020 with fault value 2
i007:
F020 with fault value 3
i008:
F020 with fault value 4
U102
Source for the activation of F033 and F053
(2102)
Selection of the binectors that activate fault messages F033 or F053 on
*
log. "1"
S00
0 = Binector B0000
(B115)
1 = Binector B0001
etc.
Up to SW 1.7: F033 (without fault value) if binector = 1 (FB 4)
SW 1.8 and later:
i001:
F033 with fault value 1 (FB 4)
i002:
F033 with fault value 2
i003:
F033 with fault value 3
i004:
F033 with fault value 4
i005:
F053 with fault value 1 (FB 288)
i006:
F053 with fault value 2
i007:
F053 with fault value 3
i008:
F053 with fault value 4
U103
Source for the activation of F034 and F054
(2103)
Selection of the binectors that activate fault messages F034 or F054 on log.
*
"1"
S00
0 = Binector B0000
(B115)
1 = Binector B0001
etc.
Up to SW 1.7: F034 (without Fault value) if binector = 1 (FB 5)
SW 1.8 and later:
i001:
F034 with fault value 1 (FB 5)
i002:
F034 with fault value 2
i003:
F034 with fault value 3
i004:
F034 with fault value 4
i005:
F054 with fault value 1 (FB 289)
i006:
F054 with fault value 2
i007:
F054 with fault value 3
i008:
F054 with fault value 4
U104
Source for the activation of A023 and A019
(2104)
Selection of the binectors that activate alarm A023 or A019 on log. "1"
*
S00
0 = Binector B0000
1 = Binector B0001
(B115)
etc.
Up to SW 1.7:
SW 1.8 and later:
i001:
i002:
11-104
A023
(FB 6)
A023
(FB 6)
A019
(FB 256)
Value range
[Unit]
Steps
All binector numbers
FB 3, FB 287
1
All binector numbers
FB 4, FB 288
1
All binector numbers
FB 5, FB 289
1
All binector numbers
FB 6, FB 256
1
SIMOREG DC Master
05.05
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 8
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 8
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 8
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
SIEMENS AG
6RX1700-0AD76
Operating Instructions