Parameter list
PNU
Description
Source for input signals, AND element 22 (output = B9371)
U341
(2341)
As for U320
*
S00
(B205)
Source for input signals, AND element 23 (output = B9372)
U342
(2342)
As for U320
*
S00
(B205)
Source for input signals, AND element 24 (output = B9373)
U343
(2343)
As for U320
*
S00
(B205)
Source for input signals, AND element 25 (output = B9374)
U344
(2344)
As for U320
*
S00
(B205)
Source for input signals, AND element 26 (output = B9375)
U345
(2345)
As for U320
*
S00
(B205)
Source for input signals, AND element 27 (output = B9376)
U346
(2346)
As for U320
*
S00
(B205)
Source for input signals, AND element 28 (output = B9377)
U347
(2347)
As for U320
*
S00
(B205)
OR elements with 3 inputs each
The input signals selected via the 3 indices of the parameter are ORed and the result of the logic operation applied to the specified
binector.
Source for input signals, OR element 1 (output = B9380)
U350
(2350)
i001
Source for input 1
*
i002
Source for input 2
S00
i003
Source for input 3
(B206)
Settings:
0 = binector B0000
1 = binector B0001
etc.
Source for input signals, OR element 2 (output = B9381)
U351
(2351)
As for U350
*
S00
(B206)
Source for input signals, OR element 3 (output = B9382)
U352
(2352)
As for U350
*
S00
(B206)
Source for input signals, OR element 4 (output = B9383)
U353
(2353)
As for U350
*
S00
(B206)
Source for input signals, OR element 5 (output = B9384)
U354
(2354)
As for U350
*
S00
(B206)
11-132
Value range
[Unit]
Steps
All binector numbers
FB 141
1
All binector numbers
FB 142
1
All binector numbers
FB 143
1
All binector numbers
FB 144
1
All binector numbers
FB 145
1
All binector numbers
FB 146
1
All binector numbers
FB 147
1
All binector numbers
FB 150
1
All binector numbers
FB 151
1
All binector numbers
FB 152
1
All binector numbers
FB 153
1
All binector numbers
FB 154
1
SIEMENS AG
SIMOREG DC Master
05.05
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
6RX1700-0AD76
Operating Instructions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents