Pentair IntelliCenter User Manual

For pool and spa
Hide thumbs Also See for IntelliCenter:
Table of Contents

Advertisement

INTELLICENTER
FOR POOL AND SPA
Air Temp 65° F
Air Temp 65° F
78°
78°
84°
84°
Pool
Pool
Schedule
Schedule
IMPORTANT SAFET Y INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
Spa
Spa
Usage
Usage
Chemistry
Chemistry
SAVE THESE INSTRUCTIONS
CONTROL SYSTEM
8:00 A.M.
8:00 A.M.
3
3
6.50
6.50
0
0
Status
Status
USER'S GUIDE
IntelliCenter Control System User's Guide
3
3
Lights
Lights
4
4

Advertisement

Table of Contents
loading

Summary of Contents for Pentair IntelliCenter

  • Page 1 8:00 A.M. 8:00 A.M. 78° 78° 84° 84° Pool Pool Lights Lights 6.50 6.50 Schedule Schedule Usage Usage Chemistry Chemistry Status Status USER’S GUIDE IMPORTANT SAFET Y INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS IntelliCenter Control System User’s Guide...
  • Page 2 IntelliCenter Control System User’s Guide...
  • Page 3: Table Of Contents

    Chemistry Readings Badges Vacation Mode (see page 38) Usage (Summary View) Show Badge Colors Alerts and Notifications 45 Usage (Summary View Edit) Security (Passcode Protect) 45 Usage (Graph Screen) Pentair User Portal Groups (Light/Circuits) P/N 522990.A 3/2018 IntelliCenter Control System User’s Guide...
  • Page 4 Down Delay IntelliCenter Control System Heater (Solar Heating) Wireless Connections Heaters Heat Pump Diagram (UltraTemp/Hybrid) IntelliCenter Control System Valves Configurations and Models 106 Valves (Installation) Optional Expansion Valve Glossary 108 Chemistry IntelliChlor/IntelliChem 78 IntelliChlor SCG IntelliChem IntelliCenter Control System User’s Guide...
  • Page 5 Failure to do so could result in death or serious injury to service person, pool users or others due to electric shock. IntelliCenter Control System User’s Guide...
  • Page 6 If necessary, consult Pentair Technical Support 1.800.731.3773 or consult an experienced radio/television technician for additional suggestions. Important: Changes or modifications to this product not authorized by Pentair could void the EMC compliance and negate your authority to operate the product. This product was tested for EMC compliance.
  • Page 7 This symbol indicates that your product must be disposed of properly according to local laws and regulations. When your product reaches its end of life, contact Pentair Technical Support 1.800.371.7333 or your local authorities to learn about recycling options. California: The coin cell battery in your remote contains perchlorates. Special handling and disposal may apply.
  • Page 8: Phone: (800)

    Phone: (800) 831-7133 Fax: (800) 284-4151 Visit www.pentairpool.com Technical Support Sanford, North Carolina (8 AM to 8 PM) Phone: (919) 566-8000 Fax: (919) 566-8920 Moorpark, California (5 AM to 5 PM) Phone: (805) 553-5000 Fax: (805) 553-5515 IntelliCenter Control System User’s Guide...
  • Page 9: Overview

    ® now control your pool and spa from anywhere inside or outside your home. The IntelliCenter Control System is a scalable system that can be used with popular home automation systems. This manual describes how use the IntelliCenter Control System and associated equipment.
  • Page 10: Navigation

    Help information. Tap the Help icon to display the contextual on-screen help information. Green: System status is good (OK) Blue: System Status Information. Orange: Warning status condition. Red: Alert status condition. Note: Badges are displayed on the Home screen Status icon. IntelliCenter Control System User’s Guide...
  • Page 11 Note: Blue Badge will stay on for the Egg Timer duration (12 hrs. default). If the Egg Timer is set to Don't Stop to circuit will run continuously until manually is switched off. IntelliCenter Control System User’s Guide...
  • Page 12: Home Screen Connection Indicators

    IntelliCenter Installation Guide. For Wireless Remote settings, see page 86. Setup Wizard and Wireless Network Bridge (www.intellicenter.com): In order to connect the IntelliCenter Control System to your home network, the Wireless Network Bridge Antenna must be connected to the IntelliCenter Load Center and your home network.
  • Page 13: Display Icon (Day/Night Theme)

    Manual Control of Equipment and Functions The Home screen displays the current pool and spa operating status. The example below shows IntelliCenter™ Control System model i5PS (pool/spa shared equipment with heater, see page 72. Tap an icon to access its control screen to manually control pool and spa equipment.
  • Page 14: Pool/Spa System Configurations

    Pool/Spa System Configurations Systems with multiple pools and/or spas (up to two bodies of water total). Depending on the Personality Card installed in the IntelliCenter™ Control System load center (see page 95) a system can be configured as follows: Single Body (model i5, i8, i10): One set of equipment for a single body of water (pool or spa).
  • Page 15: Intellicenter Control System Menu

    Network and WiFi Setup: Configure Ethernet, Connect to a Wireless Network, Adjust Wireless Transmit Power, Internet Connection Test, Reboot WiFi Device. IntelliCenter Wireless Remote Setup: Configure the Address and Panel # for wireless remote. Delays: Valve Delay, Heater Cool Down, Freeze Cycle Time (min), Spa Freeze Override (min), Override Delays.
  • Page 16: Home Screen

    The Pentair logo (IntelliCenter.com connection), Ethernet connection and the optional Wireless Remote signal and battery strength may also be displayed. The Home screen example below shows an i5PS IntelliCenter Control System (shared equipment pool and spa with heater). For IntelliCenter Control System models see page 106.
  • Page 17: Pool

    Off Fahrenheit or Celsius, see page 41. (no heat source), Heater, Solar Only, Solar Preferred, Heat Pump, UltraTemp (Hybrid) or UltraTemp (Hybrid) Preferred. Note: To add a heater, see page 72. IntelliCenter Control System User’s Guide...
  • Page 18 Source screen. Note: The Home screen displays a Blue badge over the Pool icon with the current pool water temperature. Pool Air Temp 65° F 8:00 A.M. Pool Filter Pump 78 ° °F Pool Temp Pool Features Lights 6.50 Heat Mode Off Schedule Usage Chemistry Status IntelliCenter Control System User’s Guide...
  • Page 19: Spa

    (up to nine characters), go to Settings go to Settings > Advanced System > Advanced System Configuration > Configuration > Installation Setup > Installation Setup > Body Configuration, see Circuits, see page 56. page 55. IntelliCenter Control System User’s Guide...
  • Page 20 Select Heat Source screen. Tap the Heat Mode button to display the Select Heat Source screen. Air Temp 65° F 8:00 A.M. Spa Pump 78 ° Spa Temperature ° Pool Features Lights 6.50 Heat Mode Off Schedule Usage Chemistry Status IntelliCenter Control System User’s Guide...
  • Page 21: Features

    See Installation Setup on page 53, For more about Light Groups see page 49, 56. For Feature Groups see page 58. Features Feature Groups Individual Groups Individual Groups Slide Waterfall Night Spa Pool Party Spillway PoolPump Sch1 Features Individual Groups Pump SPD 1500 Waterfall Pump SPD 3450 IntelliCenter Control System User’s Guide...
  • Page 22: Lights

    MagicStream Laminar. solenoid Thumper to create a random The new setting will be save. wrinkle in the laminar’s water stream and display a brilliant spot of light that moves along the stream’s arc. IntelliCenter Control System User’s Guide...
  • Page 23 Light Settings Light Groups Lights in Group Groups Settings Individual Groups Lights Group 1 GloBrite IntelliBrite Landscape LT Grp ColorCascade Lighting Group 1 All Lights OFF All Lights Waterfall LT Grp Continue to the next page. IntelliCenter Control System User’s Guide...
  • Page 24 Light Shows. Tap Check to return to the previous screen. Light Show Light Show AUX 4 Light Show Pool Lights Group Settings Lights in Group Groups Settings Party Light Show Lighting Mode Sunset Royalty IntelliCenter Control System User’s Guide...
  • Page 25 To change the light color or the light delay (from 0 to 60): Tap Settings > Groups. Select the group of lights to change. Tap Color Settings. Set the delays between the lights from 0 to 60 sec. IntelliCenter Control System User’s Guide...
  • Page 26 Dimmer Level levels are from 50%, 75% and 100% increments. ▲  Check: Tap Check to save changes and return to the Lights screen. X button: Tap to return to the previous screen without saving changes. IntelliCenter Control System User’s Guide...
  • Page 27: Schedule

    Heater Cool Down: Default enabled. Provides a two minute-delay in turning off the circulation pump after heater has completed its firing cycle to allow the heater to cool down. See page 72 for more information. Continue to next page. IntelliCenter Control System User’s Guide...
  • Page 28: Schedule - Weekly

    Installation Setup > Circuits and Feature Circuits, see page 56. Start Time (Manual): Set the start time Weekdays Weekdays Weekdays Everyday Everyday Every Day (am/pm) for the Weekly schedule. Everyday Weekdays Weekends Weekends Weekends Weekends Everyday Everyday No Days IntelliCenter Control System User’s Guide...
  • Page 29: Schedule - Manual Op Priority

    12 hours or whatever that circuit Egg Timer is set to, after which the scheduled program will resume if the schedule has not ended before the Egg Timer has expired. See Settings > General page 44 for more information. IntelliCenter Control System User’s Guide...
  • Page 30: Schedule - One Time Only

    12 hours or whatever that circuit Egg Timer is set to, after which the scheduled program will resume if the schedule has not ended before the Egg Timer has expired. See Settings > General page 44 for more information. IntelliCenter Control System User’s Guide...
  • Page 31 Configuration > Installation Setup > Heaters, See page 72 for more Heat Source information. Set Temperature Set Temperature: Tap the plus or minus button to set the Heat Source set point temperature from 40° F to 104° F. IntelliCenter Control System User’s Guide...
  • Page 32: Schedule - Offset Sunrise/Sunset Time

    Internet clock. If you select to use the Internet clock your computer clock should connected to the your Internet domain to synchronize automatically with a network time server, then the IntelliCenter Control System clock will be in sync with your computer time. Be sure your computer has a continuous Internet connection to maintain automatic clock synchronization.
  • Page 33: Vacation Mode (See Page 38)

    Vacation Mode. Vaction Mode Schedules Schedules Add Program Add Program Pool 8:00pm-5:00pm 8:00p-11:00p Weekdays: M Tu W Th F Wed June 14 Pool 8:00p-11:00p Everyday Pool Lights 8:00p-11:00p Weekdays: M Tu W Th F IntelliCenter Control System User’s Guide...
  • Page 34: Usage (Summary View)

    26 | Usage (Summary View) To access the Usage screen, tap the Usage icon on the Home screen. The Historical Usage data is saved when using the IntelliCenter™ Control System Outdoor, Indoor Control Panels and Wireless Remote. Summary View Graph Icon: Tap this icon to display a...
  • Page 35: Usage (Summary View Edit)

    Left and Right Buttons: Use these buttons to scroll through a selected item details from Magnifying Glass Button: Tap the magnifying glass button the to display the highest usage data for the selected item. Tap the button again to display the lowest usage data. IntelliCenter Control System User’s Guide...
  • Page 36: Usage (Graph Screen)

    Temp, Air Temp, Pool %, Spa %, Gas Heater %, Solar Heat %. After scrolling to the last item, continue to tap the Up/Down button to return to the Summary View. Also, tap the Down arrow (right side of graph screen) to display system configured AUX circuits usage data. IntelliCenter Control System User’s Guide...
  • Page 37: Chemistry

    The Tank indicator (1-6 segment) is a visual representation of the amount of muriatic acid currently in the external canister. Tap the Up or Down button to match the amount of muriatic acid in the canister. IntelliCenter Control System User’s Guide...
  • Page 38: Chemistry ( Orp Measurement)

    (up to six months). Note: Use the Up/Down arrow to scroll pH Usage through the graph. ORP Usage 3 PM 7 AM 10 AM 12 PM Tuesday Jan 24 to Wed Jan 25, 2017 IntelliCenter Control System User’s Guide...
  • Page 39: Chemistry (Water Balance)

    Total Alkalinity: 80 - 120 ppm Calcium Hardness: 200 - 400 ppm Salt: 3000 - 4500 ppm (ideal 3400 ppm) Metals: (Copper, Iron, Manganese): None Nitrates: None Phosphates: Less than 125 ppb Total Dissolved Solids: below 5000 ppm IntelliCenter Control System User’s Guide...
  • Page 40: Chemistry (Intellichlor Scg)

    Body 3 (%) displayed under the status bar. Body 4 (%) Chlorinator Status Salt Low The salt level in the chlorinator is low Chlorinator Body 1 (%) Body 2 (%) Body 3 (%) Body 4 (%) IntelliCenter Control System User’s Guide...
  • Page 41: Status

    This may be the result of Pump1 IntelliChem “Low”, you may not have a Check pH Tank sufficiently sized dose to reach the Pump3 Heater Cool-Down Delay “High” or “Off”. IntelliChem 1 pH Low IntelliCenter Control System User’s Guide...
  • Page 42 Alert messages are automatically logged for viewing. Blue!: Indicates a system status condition, such as a heater cool- down delay. Status messages are not automatically logged unless selected from the Status Selection screen. IntelliCenter Control System User’s Guide...
  • Page 43: Settings

    Security: Enable passcode protection for the IntelliCenter™ Control System. Setup system Administrator and Guest passcode. See page 45. Pentair User Portal: Login or Create New Account (enter contacts email address, property name, password). The system will attempt to connect to the account email address (via the Internet).
  • Page 44 (SSID), Adjust Wireless Transmit Power, Internet Connection, and Reboot WiFi Device. See page 84. IntelliCenter Wireless Remote Setup: Set up the wireless remote. See page 86. Delay Settings: Valve Delay ON/OFF, Heater Cool Down ON/OFF, Freeze Cycle Time (min), Spa Freeze Override (min) and Override Delays. See page 87.
  • Page 45: Service Mode

    02 Hr 56 Min 50 Sec Tap Manual Circuit Control and choose the circuits to enable. Note: Circuits selected in the Service Manual Circuit Control screen are retained in the Timer Manual Circuit Control screen. IntelliCenter Control System User’s Guide...
  • Page 46: Vacation Mode

    Vacation Stop Date: Set the vacation end month, day and year. The number days before the vacation stop date are 305 days to start Vacation shown on the screen. Vacation Stop Date 2018 61 days to stop Vacation IntelliCenter Control System User’s Guide...
  • Page 47: Support

    Check and Yes to delete contact. Support screen: Displays contact Support name, phone, Email and URL information. Name: Pentair Water Pool and Spa, Inc. Phone: (800) 831 7133 E-Mail: support@poolfyi.com URL: http://www.poolfyi.com To Add a Contact: Tap on the Support screen to Enter Contact Name.
  • Page 48: General

    Internet with the Internet connection time. If needed. Tap Date & Time to manually Clock Mode change the IntelliCenter System Control System clocks, including the Outdoor, Daylight Savings Indoor, and Wireless Remotes. If the PC time and date do not match the time and...
  • Page 49: Units

    | 41 Date & Time (Continued) (General) Time Set: Manually set IntelliCenter Date & Time system controller time, am/pm. If the Mode Manual system is connected to the Internet, resetting the system date will override Clock Mode the Internet time.
  • Page 50: Backlight

    Alphabetically (sorted Sorted in ascending order in ascending order or System sorted on System system index. Sorted based on System index Select List Order: Sort Alphabetically, Most Recent, Most Frequent or Custom Order. IntelliCenter Control System User’s Guide...
  • Page 51: Temperature Sensor Calibration

    | 43 Temperature Sensor Calibration (General) Temperature Sensor Calibration: List the installed IntelliCenter™ Control System sensors (ambient air, pool and solar (if installed). The current sensor temperature is displayed. Tap sensor name bar to access Sensor Calibration screen. Sensor Calibration: Adjust the sensor temperature value. Use Up/Down arrow to Increase or decrease temperature value compared to actual reading.
  • Page 52: Day/Night Themes

    Day or Night Theme modes. Auto: This option will automatically transition between Day and Night screen mode based on the IntelliCenter™ Control System 24 hour clock. Manual Operation Priority (General) Manual OP Priority: ON: This feature allows for a circuit to be manually switched...
  • Page 53: Security (Passcode Protect)

    Timeout (min): Tap the plus or minus button to set the screen elapse time (1-10 minutes) before a screen message is displayed for the passcode. Note: A padlock icon displayed on the Home screen (top right) indicates there is an Administrator logged in (passcode assigned to the system). IntelliCenter Control System User’s Guide...
  • Page 54 Note: If the incorrect Passcode is entered multiple times, the Access Denied screen is displayed. This screen will time out for 60 seconds. After 60 seconds has elapsed, tap OK to enter the correct Passcode. IntelliCenter Control System User’s Guide...
  • Page 55: Pentair User Portal

    Password. The system will attempt to connect to the owner's account Email address (via the Internet) to www.intellicenter.com. Connecting to your pool using the Web App: Go to www.intellicenter.com and sign in using the pool owner's user email address. Select your pool listed on the Installations screen to display the Home screen.
  • Page 56: Groups (Light/Circuits)

    Advanced System Configuration > AUX 2 Pool Pump Installation Setup > Circuits > AUX Function: IntelliFlo Circuit (page 56) and Feature Waterfall Booster Pump Function: Generic Circuits (page 58). AUX 5 AUX 5 Function: Generic AUX Circuits Screen IntelliCenter Control System User’s Guide...
  • Page 57 Dont Stop: Tap the Hours button until 23 hours is displayed, then tap the button again to display Do Not Stop. The Do Not Stop feature will continuously run the circuit until the it is manually turned off. IntelliCenter Control System User’s Guide...
  • Page 58: Groups (Lights)

    Color Swim Settings a different color for the light from the Pool Light list. Color Name Delays(s): Tap the - /+ button to set the White Color delay for the light from 0 to 60 seconds. Delays(s) IntelliCenter Control System User’s Guide...
  • Page 59: Groups (Feature Circuits)

    Tap cancel to stop the system reset. This feature has the same system reset function using the Reset Button on the Wireless Remote cradle, and on the front of the Indoor or Outdoor Control Panel. See page 35. IntelliCenter Control System User’s Guide...
  • Page 60: Settings (Advanced System Configuration)

    IntelliCenter Wireless Remote Setup: Configure Ethernet, Connect to a Wireless Network (SSID), Test Internet Connection and Reboot WiFi Device. See page 84. IntelliCenter Wireless Remote Setup: Set up the wireless remote. See page 86. Delays: Valve delay settings, Heater Cool Down ON/OFF, Freeze cycle time (min), Spa Freeze override (mins) settings.
  • Page 61: Installation Setup

    Pool Cover Pool Cover: Setup Pool Cover circuit settings, see page 79. Body Configuration: Configure the IntelliCenter™ Control System Personality Cards, (Main Panel (OCP0), Expansion enclosures 1, 2, and 3), and the body of water capacity for the pool and spa.
  • Page 62: Panel Identification

    Body Name: Enter the body name. Body capacity: Enter the capacity of Expansion 1 (disabled) XCP0 the body of water from 1000 - 40,000 Select Body 1 Type for Master Panel gallons (US gallons/liters). Expansion 2 (disabled) XCp1 Pool IntelliCenter Control System User’s Guide...
  • Page 63: Expansion Panels

    Daughter Card connected to the main Personality board (in this example i10x (10 Relays). Tap the Expansion Panel Daughter Card button to enable the card (Green light on). See page 106 for more information about IntelliCenter™ Control Panel system configurations. IntelliCenter Control System User’s Guide...
  • Page 64 See page again to display Do Not Stop. The Do Not 59 for details. Stop feature will continuously run the circuit until the it is manually turned off. IntelliCenter Control System User’s Guide...
  • Page 65: Feature Circuits

    Changing the circuit type will reset all type-specific Note: The Egg Timer sets a specified time delay (hrs/mins) for the circuit to Generic Spillway function once it is turned on. Freeze Protection: Assign freeze protection for the circuit. See page 59. IntelliCenter Control System User’s Guide...
  • Page 66 Don't Stop: Tap the Hours button until 23 hours is displayed, then tap the button again to display Do Not Stop. The Do Not Stop feature will continuously run the circuit until the it is manually turned off. IntelliCenter Control System User’s Guide...
  • Page 67 PROTECTION is set to ON. For all other equipment, Freeze Protect must also be specified on the individual device manager screen. Some devices default to freeze protect. Heater Operation During Freeze Protection: The heater will not activate during a Freeze Protection period unless it is manually turned on. IntelliCenter Control System User’s Guide...
  • Page 68: Circuit Functions

    - Force the filter pump on five (5) minutes before the cleaner. - Turn the cleaner off when the spa is on. - Turn the cleaner off for five (5) minutes when the solar heating begins. IntelliCenter Control System User’s Guide...
  • Page 69: Circuit Names

    SLIDE FOUNTAIN 3 FOUNTAIN LIGHT FOUNTAINS SPA HIGH FRONT LIGHT SPA LIGHT GARDEN LIGHT SPA LOW GAZEBO LIGHT SPA SAL HIGH SPEED SPA SAM HIGH TEMPERATURE SPA WATERFALL IN-FLOOR CLEANER SPILLWAY INFINITY EDGE SPRINKLERS JETS IntelliCenter Control System User’s Guide...
  • Page 70: Pumps

    5 minutes of heater cool down period. You can override the heater cool down period by taping the button again to turn off the filter pump. IntelliCenter Control System User’s Guide...
  • Page 71: Pumps (Dual Speed)

    5 minutes of heater cool down period. You can override the heater cool down period by taping the button again to turn off the filter pump. IntelliCenter Control System User’s Guide...
  • Page 72: Pumps (Intelliflo Vs)

    0-5 Pump Address minutes. Min Speed (RPM) Priming Speed (RPM): The system 3450 priming speed can be set from Max Speed (RPM) 450-3450 RPM. Step Size (I/min) Prime Time (min) 2500 Priming Speed (RPM) IntelliCenter Control System User’s Guide...
  • Page 73 OK - No Problems Detected see: Tap Status on the Home screen to Pump appears to be running normally. Click display the current pump status and here to view possible issues not being detected. error condition. IntelliCenter Control System User’s Guide...
  • Page 74: Pumps (Intelliflo Vsf)

    The pump will not allow a higher flow rate of 140 GPM to prevent damage to the pool system hydraulics. Step Size (RPM): The pump speed step size can be set from 10-250 RPM. Step Size (GPM): The pump flow rate step size can be set from 1-10 GPM. IntelliCenter Control System User’s Guide...
  • Page 75 1600 RPM see: Tap Status on the Home screen to No Problems Detected display the current pump status and Pump appears to be running normally. Click error condition. here to view possible issues not being detected. IntelliCenter Control System User’s Guide...
  • Page 76: Pumps (Intelliflo Vf)

    Minimum Flow (GPM): The pump's minimum flow rate can be set from 15-130. This is the minimum flow rate speed but still generating sufficient flow in the pool. The IntelliCenter™ Control System will not run lower than 15 GPM. The lower you can establish this flow rate the better the energy savings.
  • Page 77: Intelliflo Pump Alarms And Warnings

    The drive contains capacitors that keep it powered up long enough to save the current run parameters. If power is restored during this process, approximately 20 seconds, the drive will not restart until completed. Continue to next page. IntelliCenter Control System User’s Guide...
  • Page 78 Freeze Protection ON in the pump circuit option in the IntelliCenter™ Control System menu (see page 62). To re-enable the internal thermal protection, the power to the drive must be cycled off then back on.
  • Page 79 (Continued) Internal Error Indicates that the self-monitoring motor control software has encountered an error. Clear the alarm and restart the pump. If this alarm persists, contact Pentair Technical Service at 1-800-831-7133. Speed Limit (Warning) The pump has detected that it has met the maximum allowed speed set in the Min/ Max menu.
  • Page 80: Heaters (Gas)

    0 to 10 minutes (5 min. default). Cool Down Delay (min) Note: Pentair gas heaters do not require a cool down period. Add Heaters: IntelliCenter™ Control System supports the following heater configurations: • Gas Heater • Solar Heater • Heat Pump •...
  • Page 81: Solar And Heat Pump

    See page 74. Air Temp 65° F 8:00 A.M. Pool Heating 78° 85° Pool Set Point ° ° Pool Temp Pool Features Lights Cooling Set Point ° Heat Mode Schedule Usage Chemistry Status IntelliCenter Control System User’s Guide...
  • Page 82: Heater (Solar Heating)

    ON. Example: Water Temperature is 75°F; The target temperature is 82°F. When the roof solar collectors temperature exceeds the water temperature by 6° Start Temp Delta (81°F), the solar valve rotates. If a solar booster pump is required, this pump will turn on. IntelliCenter Control System User’s Guide...
  • Page 83: Heaters Heat Pump

    Cooling Enabled (UltraTemp only): On/Off: On: Provides cooling for pools that overheat in hot climates. When enabled, circulates pool water through the exchanger and draws heat from the water and expels it through the fan. IntelliCenter Control System User’s Guide...
  • Page 84: Valves

    Valve A is for pool, and Valve B for spa. Installing the optional Valve Expansion Card provide an additional six (6) valve actuators (C, D, E, F G). See IntelliCenter Control System Models in Settings > Advanced System Configuration > Installation Setup > Body Configuration, see page 55.
  • Page 85: Optional Expansion Valve

    Standard Configuring Valve Actuators (Controlled by AUX or Feature Circuit) The IntelliCenter™ Control System can control two auxiliary valve actuators (A and B) for applications such as solar heating and water features. With the addition of the Valve Expansion Card, the system can accommodate up to six (6) additional actuators (C, D, E, F, G, H) for a total of eight (8) actuators.
  • Page 86: Chemistry

    Body 1 (pool), Body 2 (Spa). (*) Show/Hide IntelliChem Badge on Home Screen: Go to Settings > General > Address Chemistry Readings Badge to show pH Body 1 Pool and ORP readings (set to ON or OFF). Body 2 IntelliCenter Control System User’s Guide...
  • Page 87: Pool/Spa Cover

    Pool or Spa Cover Position: "OPEN" and "COVERED" is displayed on the Home screen to indicate the current position of the cover. The cover connection is via an RS-485 COM Port on the IntelliCenter™ Control System Expansion Card. Pool Cover Settings:...
  • Page 88: Remotes Setup

    Yes to delete the selected remotes. Spillway Pump VS #2 Note. The iS4 remote (P/N 521885) iS4 Button Assignment requires a wired RS-485 connection to a COM port on main circuit board in the load center. IntelliCenter Control System User’s Guide...
  • Page 89: Quicktouch Ii Remote

    Delete Remote: From Remotes screen Select Remote Type Changing the remote type will reset all type-specific SpaCommand iS10 QuickTouch tap the Trash Can icon, select the remotes to delete and tap Check. Tap Yes to delete the selected remotes. IntelliCenter Control System User’s Guide...
  • Page 90: Is10 Remote

    Note: The iS10 remote requires a wired Circuits). RS-485 connection to a COM port on main Address Mode ON/OFF: Tap this button circuit board in the load center. enable or disable the assigned Remote Channel (1-4). IntelliCenter Control System User’s Guide...
  • Page 91: Spacommand Remote

    Configuration > Installation Setup > wired RS-485 connection to a COM port on Circuits). main circuit board in the load center. Address Mode ON/OFF: Tap this button enable or disable the assigned Remote Channel (1-4). IntelliCenter Control System User’s Guide...
  • Page 92: Network And Wifi Setup

    Outdoor Control Panel. Note: See page 47 for Pentair User Portal > Enable Web & Mobile Interface (ON) to enable the PC Web App and Mobile Interfaces to allow local network and Internet communications.
  • Page 93 Configure Network the Configure Wireless Network button Configure Ethernet IP: 192.168.1.9 to display the available wireless within range of the IntelliCenter™ Control Connect to a Wireless Network System wireless antenna. Adjust Wireless Transmit Power Available Networks: Displays the available wireless networks within Internet Connection Test range of the IntelliCenter™...
  • Page 94: Intellicenter Wireless Remote Setup

    522036. This kit includes a Wireless Transceiver with antenna which connects to an RS-485 COM port on the Outdoor Control Panel circuit board located in the load center. Note: IntelliCenter Control System settings made on the Outdoor and Indoor Control Panels and the Wireless Remote are synchronized to have the same system settings on each control panel.
  • Page 95: Delays

    Some heaters require a cool-down cycle before being turned off. This can be accomplished with a setup procedure in the IntelliCenter™ Control System which runs the filter pump an additional five (5) minutes to dissipate residual heat built up inside the heater combustion chamber.
  • Page 96: System

    System diagnostic information. ACK (Pumps) ACK (iChlor) ACK (iChem) ACK (UTemp) Check for Update: Tap this button to ACK (others) check for the latest IntelliCenter™ Slot Time Control System firmware version. System Time: Sat Nov 11 00:51:06 2017 Days Offset: 0 days Follow the screen prompts.
  • Page 97: Import/Export

    Import for USB: Insert a USB device into the USB Port on the front of the IntelliCenter™ Control System Outdoor Control Panel or the Wireless Remote. Tap Import from USB and navigate to the system configuration file .cfg). Follow the on screen instructions to import the system configuration files.
  • Page 98: Export System Config

    Save Locally 77pkplace 996nlsd Export Local Configuration to USB Select Configuration file to Export Select Configuration file to Export 121ndrive 556sunsetblvd\ 120422_556sunsetblvd.cfg 556sunsetblvd 110802_556sunsetblvd.cfg 77pkplace 120323_239elm.cfg 120315_41oakst.cfg Are you sure you want to replace the 120422_256sunsetblvd.cfg IntelliCenter Control System User’s Guide...
  • Page 99: Restore Factory Defaults

    | 91 Restore Factory Defaults [Advanced System Configuration] Restore Factory Defaults: Use this feature to overwrite the IntelliCenter™ Control System configuration with the default factory configuration settings. Tap Settings > Advanced System Configuration > Restore Factory Defaults. Tap the Restore Factory Defaults...
  • Page 100: Setup Wizard

    Pentair User Portal screen. From there you can setup either a Wireless or Ethernet connection to connect to the Internet and add a new account or login using an existing account, which includes setting up a password, pool system's owner's name, address and contact information.
  • Page 101: Intellicenter Control System

    Wizard Setup screen). Example: Before each Wizard configuration screen a YES/NO option screen is displayed. Tap YES then NEXT to enter the item configuration screen. Tap NO then NEXT to continue to the next option. IntelliCenter Control System User’s Guide...
  • Page 102: Intellicenter Control System

    Initial System Power Up First Time Setup: After all required pool/spa equipment has been connected to the IntelliCenter Control System, apply power to the system at the main panel circuit breaker. Upon the initial system power up, the outdoor LCD control panel will display the PENTAIR END USER LICENSE AGREEMENT.
  • Page 103 | 95 Setup Wizard [Advanced System Configuration] Import for USB: Insert a USB device into the USB Port on the IntelliCenter™ Control System Outdoor or Indoor control panel. Tap Import from USB and navigate to the system configuration file (.CFG). Follow the on screen instructions to import the system configuration files plugged into the USB Port on the Outdoor or Indoor control panel.
  • Page 104: Intellicenter Control System

    1 AUX Circuit has been configured. AUX Circuits, tap Next to continue to Tap Next to modify an existing AUX Circuit setting. Feature Circuits. Exit Help/ Back/ Next/ Wizard Summary Menu Home IntelliCenter Control System User’s Guide...
  • Page 105: Intellicenter Control System

    Assigned Circuit for Valve A or Valve B: Tap unassigned, and select an AUX circuit for the valve. Tap Check to return to the previous screen. Tap Valve name, enter the new valve name then tap Check to save and return to the previous screen. IntelliCenter Control System User’s Guide...
  • Page 106: Intellicenter Control System

    Two Speed Pump Settings: Tap Settings: Pump Type (select a different type of pump), Pump Name, Low Speed Circuit and High Speed Circuits. Select a circuit for the low speed and the high speed. You can choose up to (4) four high speed circuits. IntelliCenter Control System User’s Guide...
  • Page 107: Intellicenter Control System

    • Button Assignments: Tap Configure. Tap Button 1, then tap the AUX circuit button for this circuit. Tap Back and repeat for buttons 2-4. When all buttons have been assigned, tap Return arrow until SpaCommand remote screen is displayed. Tap Next to continue. IntelliCenter Control System User’s Guide...
  • Page 108: Intellicenter Control System

    Set the run time percentage to produce chlorine. The higher the percentage the more chlorine is produced. Lower the percentage for less chlorine production. Note: See page 78 for information about the IntelliChem Controller and IntelliChlor SCG. IntelliCenter Control System User’s Guide...
  • Page 109: Intellicenter Control System

    Brooklyn, NY Date & Time United States 11220 Zip Code 11220 Time Zone East Time (US & Canada) UTC-4 AUX Circuits 4 Circuits are configured Help/ Exit Back/ Next Menu Wizard Home Continue to next page. IntelliCenter Control System User’s Guide...
  • Page 110 Finish: Save the configuration and go to the Home screen. "Applying Settings" is displayed, then the Home screen is displayed. The Setup Wizard has been successfully completed. Air Temp 65° F 8:00 A.M. 78° 84° Pool Features Lights 6.50 Schedule Usage Chemistry Status Home Screen IntelliCenter Control System User’s Guide...
  • Page 111: Intellicenter Control System Remote Access Instructions

    For the initial system setup, enter your zip code and location. The next screen to display is the Pentair User Portal screen. From there you can setup either a Wireless or Ethernet connection to connect to the Internet. Add a new account or login using an existing account, which includes setting up a password, pool system's owner's name, address and contact information.
  • Page 112: Power

    Checkmark 16. Tap the Checkmark to complete the process. Once the account setup is complete, return to the home screen and wait for the Pentair logo to appear. After the Pentair logo appears you are connected to www.intellcenter.com and should be able to remotely connect to your IntelliCenter Control System using your User Name and Password used previously.
  • Page 113: Intellicenter Control System Wireless Connections Diagram

    | 105 IntelliCenter Control System Wireless Connections Diagram ™ IntelliCenter Control System User’s Guide...
  • Page 114: Intellicenter Control System Configurations And Models

    Shared equipment (Pool and Spa) Filter pump relay+ 9 AUX relays Intake and Return valves Same as i5P (see i5P for details) OCP0 i10D i10D Capabilities: Dual Bodies of water with separate Pumps, Filters and Heaters IntelliCenter Control System User’s Guide...
  • Page 115 Exp Motherboard - i5X or i10X OCP1-4 VALVEXP Valve Expansion module: six extra valve outputs (C, D, E, F, G & H) OCP1-4 Allows external input for system control A TO DXP (eg. Pool Cover) Analog/Digital Expansion module: IntelliCenter Control System User’s Guide...
  • Page 116: Glossary

    Host computer: The computer that is directly connected to the Internet using a modem or network adapter. Indoor Control Panel: The IntelliCenter™ Control System color touch LCD screen is wired to the Personality board in the Power/Load Center. The control panel can be wall mounted inside a house.
  • Page 117 Megabits-per-second ( Mbps): Transmission speed of 1,000,000 bits per second. Megahertz (MHz): A unit of frequency equal to 1,000,000 cycles per second. Wireless Controller: Wireless controller for IntelliCenter™ Control Systems with all the functionality of the Indoor Control Panel. Outdoor Control Panel: LCD color touch control panel with flexible hinge is installed in upper portion of Power/Load Center and connected to the main circuit board (iS5).
  • Page 118 110 | Notes IntelliCenter Control System User’s Guide...
  • Page 119 | 111 IntelliCenter Control System User’s Guide...