A-5 Safety CPU Unit Status

The Safety CPU Unit status gives the operating status of the Safety CPU Unit. When a Safety CPU
Unit is placed on the NX bus of the Communications Coupler Unit, the status is displayed as an I/O
port in the I/O map of the Communications Coupler Unit. Also, when a Safety CPU Unit is placed on
the NX bus of the NX-series CPU Unit, the status is displayed as an I/O port in the I/O map of the CPU
rack.
If you set a device variable for the I/O port, you can monitor the status of the Safety CPU Unit from the
NJ/NX-series CPU Unit.
A-5-1

NX-SL3300/NX-SL3500

I/O port
Safety CPU Sta-
tus
D00 Normal
Operating
D01 Program
Operating
D02 Program
No Fault
D03 Safety
Master
Connec-
tion Status
A-5-2

NX-SL5500/NX-SL5700

I/O port
Safety CPU Sta-
tus
A - 72
Description
Status monitoring
This is a WORD variable that contains the following
data for the Safety
status.
CPU Unit
Safety programs op-
This variable is TRUE when all of the following con-
erating with no er-
ditions are met. If even one condition is not met, it is
rors.
FALSE.
All safety master
Conditions
connections estab-
The safety programs are in RUN status (RUN
lished.
mode or DEBUG mode (RUN)).
No event with a level of minor fault or higher cur-
rently exists for the safety programs.
All FSoE connections are established.
Safety programs op-
This variable is TRUE when the following condition
erating
is met. If the condition is not met, it is FALSE.
Condition
The safety programs are in RUN status (RUN
mode or DEBUG mode (RUN)).
No event with a level
This variable is TRUE when the following condition
of minor fault or high-
is met. If the condition is not met, it is FALSE.
er currently exists for
Condition
the safety programs.
No event with a level of minor fault or higher cur-
rently exists for the safety programs.
All safety master
This variable is TRUE when the following condition
connections estab-
is met. If the condition is not met, it is FALSE.
lished.
Conditions
All FSoE connections are established.
Description
Status monitoring
This is a UINT variable that contains the following sta-
data for the Safety
tus.
CPU Unit
Condition
Condition

NX-series Safety Control Unit User's Manual (Z930)

R/
Data
W
type
R
WORD
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R/
Data
W
type
R
UINT