3 Installation and Wiring
Preventing Incorrect Attachment of Terminal Blocks
In order to prevent unintentionally installing the wrong terminal block, you can limit the combination of
a Unit and a terminal block.
Insert three Coding Pins (NX-AUX02) into three of the six incorrect attachment prevention holes on the
Unit and on the terminal block. Insert these pins into positions so that they do not interfere with each
other when the Unit and terminal block are connected to each other.
You can use these pins to create a combination in which the wrong terminal block cannot be attached
because the pin patterns do not match.
Terminal block
l Types of Coding Pins
There are two types of Coding Pins, both with their own unique shape: one for terminal blocks and
one for Units.
Three pins come with each runner.
For terminal block
Use the following Coding Pins.
Name
Coding Pin NX-AUX02 For 10 Units (Terminal block: 30 pins, Unit: 30 pins)
3 - 20
Unit
Cannot be
attached.
For Unit
Runners
Coding Pins (Use this part.)
Model
Specification
NX-series Safety Control Unit User's Manual (Z930)