Siemens SIMATIC S7-1500 Manual page 47

Analog input module ai 4xu/i/rtd/tc st (6es7531-7qd00-0ab0)
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Errors/accuracies
Linearity error (in relation to input range), (+/-)
Temperature error (in relation to input range), (+/-) 0.005%/K; for TC typ. T 0.02 +/- %/K
Crosstalk between the inputs, max.
Repeat accuracy in settled state at 25 °C (in rela-
tion to input range), (+/-)
Temperature errors of internal compensation
Operational limit in the entire temperature range
Voltage in relation to input range, (+/-)
Current in relation to input range, (+/-)
Resistance in relation to input range, (+/-)
Resistance thermometer in relation to input range,
(+/-)
Thermocouple in relation to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage in relation to input range, (+/-)
Current in relation to input range, (+/-)
Resistance in relation to input range, (+/-)
Resistance thermometer in relation to input range,
(+/-)
Thermocouple in relation to input range, (+/-)
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Series mode interference (peak value of interfer-
ence < rated value of input range), min.
Common mode voltage, max.
Common mode interference, min.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Diagnostics function
Interrupts
Diagnostic interrupt
Limit interrupt
Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0)
Manual, 09/2016, A5E32366209-AC
Technical specifications
6ES7531-7QD00-0AB0
0.02%
-80 dB
0.02%
+/-6 °C
0.3%
0.3%
0.3%
0.3%; Ptxxx Standard: ±1.5 K, Ptxxx Climatic:
±0.5 K, Nixxx Standard: ±0.5 K, Nixxx Climatic:
±0.3 K
0.3%; Type B: > 600 °C ±4.6 K, Type E: > -200
°C ±1.5 K, Type J: > -210 °C ±1.9 K, Type K: > -
200 °C ±2.4 K, Type N: > -200 °C ±2.9 K, Type
R: > 0 °C ±4.7 K, Type S: > 0 °C ±4.6 K, Type T:
> -200 °C ±2.4 K
0.1%
0.1%
0.1%
0.1%; Ptxxx Standard: ±0.7 K, Ptxxx Climatic:
±0.2 K, Nixxx Standard: ±0.3 K, Nixxx Climatic:
±0.15 K
0.1%; Type B: > 600 °C ±1.7 K, Type E: > -200
°C ±0.7 K, Type J: > -210 °C ±0.8 K, Type K: > -
200 °C ±1.2 K, Type N: > -200 °C ±1.2 K, Type
R: > 0 °C ±1.9 K, Type S: > 0 °C ±1.9 K, Type T:
> -200 °C ±0.8 K
40 dB
10 V
60 dB
No
Yes
Yes
Yes; two high limits and two low limits each
47