Parameters/address space

4.1

Measurement types and ranges

Introduction
The module is set to voltage measurement type with measuring range ±10 V by default. You
need to reassign the module parameters with STEP 7 if you want to use a different
measurement type or range.
Deactivate the input if it is not going to be used. The module cycle time is shortened and the
interference factors that lead to failure of the module (for example, triggering a hardware
interrupt) are avoided.
Measurement types and ranges
The following table shows the measurement types and the respective measuring range.
Table 4- 1
Measurement type
Voltage
Current 2WMT
(2-wire transmitter)
Current 4WMT
(4-wire transmitter)
Resistor
(2-wire connection)
Resistor
(3-wire connection)
(4-wire connection)
Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0)
Manual, 09/2016, A5E32366209-AC
Measurement types and measuring ranges
Measuring range
±50 mV
±80 mV
±250 mV
±500 mV
±1 V
±2.5 V
1 V to 5 V
±5 V
±10 V
4 mA to 20 mA
0 mA to 20 mA
4 mA to 20 mA
±20 mA
PTC
150 Ω
300 Ω
600 Ω
6000 Ω
Representation of analog values
See Representation of analog values
in voltage measuring ranges (Page 65)
See Representation of analog values
in the current measuring ranges
(Page 66)
See Representation of the analog
values of resistance-based sen-
sors/resistance thermometers
(Page 67)