Parameter data records
B.2 Structure of a data record for dynamic reference temperature
Valid values for fixed temperature compensation
You can enter the selectable values at bytes 2 and 3 of the data record for the corresponding
channel. The selectable values must lie within the permitted value range, see following table.
The resolution is a tenth of a degree.
Table B- 13
Temperature unit
Celsius (default)
Fahrenheit (default)
Kelvin (default)
Celsius (climatic)
Fahrenheit (climatic)
Kelvin (climatic)
Additional information
For more information on compensation of the reference junction temperature via data record
refer to the Analog value processing
(http://support.automation.siemens.com/WW/view/en/67989094) function manual in the
internet.
62
Valid values for temperature compensation via data record
Dec
-1450 to 1550
-2290 to 3110
1282 to 3276
-14500 to 15500
-22900 to 31100
12820 to 32760
Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0)
Hex
FA56
to 60E
H
H
F70E
to C26
H
H
502
to CCC
H
H
C75C
to 3C8C
H
H
A68C
to 797C
H
H
3214
to 7FF8
H
H
Manual, 09/2016, A5E32366209-AC